Commissioning (software) 
 
4.3 Configuring the system in online mode 
 
D410 
74
 
Commissioning Manual, 08/2008 Edition 
4.3.2 
Establishing the online connection 
The procedure for an initial commissioning follows. 
To perform an online configuration, you must establish an online connection to the 
SIMOTION D410. In this case, no connection can yet be established to SINAMICS 
Integrated. An appropriate message is output. Once the hardware configuration has been 
loaded into the target device, an online connection to the SINAMICS Integrated is 
established automatically. Proceed as follows:  
1.  Save and compile the project. 
2.  Establish an online connection. 
3.  Select the SIMOTION D410 device in the Project Navigator. 
 
 
 
Note 
Ensure that you use the "Download to the target device" function rather than "Download 
to the target system". An automatic commissioning is no longer possible after "Download 
to the target system". If "Download to the target system" has been used, "Restore factory 
settings" must be performed on the drive element in order to start an automatic 
commissioning afterwards. 
4.  Use the "Download to the target device" function to download the SIMOTION D410 
device into the target device. The connection to SINAMICS Integrated is activated 
automatically. 
You can now run the automatic configuration at SINAMICS Integrated. For details, see 
Additional references 
Further information about establishing an online connection to the programming device / PC 
is contained in the following documentation: 
● 
SIMOTION SCOUT
 Configuration Manual 
● 
SIMOTION SCOUT
 Online Help 
●  In FAQ on the 
"Utilities & Applications"
 CD