Commissioning (software) 
 
4.3 Configuring the system in online mode 
D410 
Commissioning Manual, 08/2008 Edition 
75
 
4.3.3 
Starting automatic configuration 
Prerequisites 
●  You activated the online connection to SINAMICS Integrated. 
●  You have not yet configured any drive objects. 
●  The default settings of SINAMICS Integrated were activated. 
Right-click SINAMICS Integrated" and select the "Target device" > "Restore defaults" 
command from the shortcut menu in SIMOTION SCOUT in order to restore the factory 
settings. 
Procedure 
1.  Open the "Automatic Configuration" dialog box by selecting the "SINAMICS_Integrated > 
Automatic configuration" command in the Project Navigator. 
 
Figure 4-12  Starting automatic configuration 
 
2.  Click "Start automatic configuration". 
The "Drive Object Type" dialog box opens. 
 
Figure 4-13  Selecting the drive object type