Amana HRV-150D Benutzerhandbuch

Seite von 28
1
Heat Recovery
Ventilators
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
HRV-150 • HRV-150D
HRV-200 • HRV-200D • HRV-300D
Your ventilation system should be installed in conformance with the appropriate provincial or state requirements or in the absence
of such requirements with the current edition of the National Building Code, and / or ASHRAE’s “ Good Engineering Practices”.
IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT
CAUTION - 
Before installation, careful consideration must be given to how this system will operate if connected to any other piece of mechanical equip-
ment, i.e. a forced air furnace or air handler, operating at a higher static. After installation, the compatibility of the two pieces of equipment must be confirmed
by measuring the airflow’s of the Heat Recovery or Energy Recovery Ventilators by using the balancing procedure found in this manual.
It is always important to assess how the operation of any HRV/ERV may interact with vented combustion equipment (i.e. Gas Furnaces, Oil Furnaces, Wood
Stoves, etc.).
NEVER - 
install a ventilator in a situation where its normal operation, lack of operation or partial failure may result in the backdrafting or improper function-
ing of vented combustion equipment!!!
Goodman is a registered trademark of Goodman Company, L.P.
Amana is a registered trademark of Maytag Corporation and used under license to Goodman Company, L..P.  
All rights reserved.
    
 
 
 
 

Zusammenfassung der Spezifikationen benutzerhandbuch für Amana HRV-150D

  • Seite 1 Heat Recovery Ventilators HRV-150 • HRV-150D HRV-200 • HRV-200D • HRV-300D IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING...
  • Seite 2 TABLE OF CONTENTS TECHNICAL DATA HRV(D) Series .................................................................................................. 3 HRV Series ...................................................................................................... 5 HRV-300D.................................................................................................... ...7 OPERATION............................................................................................................11 Modes Of Operation...
  • Seite 3: HRV(D) Series HRV Series HRV 150D & HRV 200D SPECIFICATIONS CASE 22 gauge galvanized steel on the HRV-200D & 24 gauge...
  • Seite 4 HRV-150D & HRV-200D 5 port for recirculation defrost type models only Dimensions TH E 6" A B C D...
  • Seite 5: HRV Series HRV Series HRV 150 & HRV 200 SPECIFICATIONS CASE 22 gauge galvanized steel on the HRV-200 & 24 gauge...
  • Seite 6 HRV-150 & HRV-200 Dimensions E 6" B D A C Model A B C D E HRV-150 2 ¹⁄₄"...
  • Seite 7 HRV Series HRV-300D SPECIFICATIONS CASE 22 gauge galvanized steel. Baked powder coated paint. Insulated with 1" (25 mm) high...
  • Seite 8 HRV-300D Dimensions 5 port for recirculation defrost TH type models only 22.20" 564mm 6" 2.20" 50.87" 2.20" 17.36" 56mm...
  • Seite 9OPERATION A Heat Recovery Ventilator (HRV) is designed to bring fresh air into a building while exhausting an equal amount...
  • Seite 10 OPERATION (CONT'D) PRACTICAL OPTIONAL REMOTE CONTROLS * All controls are low voltage. 18 to 24 gauge wire is recommended....
  • Seite 11: Modes Of OperationOPERATION (CONT'D) OPTIONAL DIGITAL CONTROL DIGITAL DISPLAY DEHUMIDISTAT CONTROL Shows Indoor Humidity Level A Dehumidistat is ideal for use in...
  • Seite 12: Digital Multi-Function Controls w/recirculation INSTALLATION PRACTICAL TIPS LOCATION The HRV must be located in a heated space where it will be possible to...
  • Seite 13: Digital Multi-Function ControlsINSTALLING DUCTS GOING TO / FROM OUTSIDE A well designed and installed ducting system will allow the HRV to operate...
  • Seite 14: Mounting the Unit INSTALLING DUCTS TO / FROM INSIDE To maximize airflow in the ductwork system, all ducts should be kept short...
  • Seite 15: Location & DuctingINSTALLING DUCTS TO / FROM INSIDE (CONT'D) Exhaust Air Ducting The stale air exhaust system is used to draw air...
  • Seite 16 INSTALLATION EXAMPLES It is the responsibility of the installer to ensure all ductwork is sized and installed as designed...
  • Seite 17INSTALLATION EXAMPLES (CONT'D) Example diagram only-duct configuration may change depending on model DIRECT CONNECTION of the SUPPLY AIR STREAM to...
  • Seite 18: Examples INSTALLATION EXAMPLES (CONT'D) Example diagram only-duct configuration may change depending on model DIRECT CONNECTION of both the HRV SUPPLY...
  • Seite 19INSTALLATION EXAMPLES (CONT'D) Example diagram only-duct configuration may change depending on model DIRECT CONNECTION of both the HRV SUPPLY AIR...
  • Seite 20 AIR FLOW BALANCING CAUTION • If the unit’s airflows are not properly balanced... - The unit may not operate...
  • Seite 21AIR FLOW BALANCING (CONT'D) AIRFLOW STATION (GRID) METHOD B 1 For this flow measuring station, cut 2 Before taking the...
  • Seite 22: Air Flow Balancing MAINTENANCE CAUTION MAKE SURE UNIT IS UNPLUGGED BEFORE ATTEMPTING ANY MAINTENANCE WORK The following components should also be inspected...
  • Seite 23TROUBLESHOOTING Problem Causes Solutions Air is too dry Dehumidistat control is set too low Increase the desired level of humidity....
  • Seite 24: MAINTENANCE ELECTRICAL CONNECTIONS Low Voltage Control Wiring Connections * Please see instruction on individual controls for proper wiring and set...
  • Seite 25: TROUBLESHOOTING ELECTRICAL CONNECTIONS (CONT'D) 3 position mode selection switch Accessory Control Contact (Open & Closes contact when HRV/ERV is ON/OFF)...
  • Seite 26: ELECTRICAL CONNECTIONS26
  • Seite 2727
  • Seite 28United States Canada The product is manufactured by Fantech, Inc. Fantech reserves the 1712 Northgate Blvd., 50 Kanalflakt Way, right...