Blodgett b12c-b Benutzeranleitung

Seite von 72
S
AFFIRE 
S
ERIES 
S
ECTIONAL 
R
ANGE
 
I
NSTALLATION
 
O
WNER
'
M
ANUAL 
1184743 P
AGE 
27
 OF 
72 
2.  Slide each flue riser down onto the brackets projecting from the back of the corresponding section(s) of the 
sectional range. Secure the flue riser to the brackets with the four provided 1/4-20x3/4 hex-head bolts, flat 
washers, and lockwashers. Also, secure the bottom edge of the flue riser to the top rear edge of the sectional 
range using the provided #10 sheet metal screws. 
3.  If access to the interior of the flue riser is necessary to make gas connections, make those connections at this 
time. 
4.  Attach each wall shield to the back of the corresponding flue riser using the provided #10 sheet metal screws. 
5.  Connect the top side edges of adjoining flue risers using the provided small plates and screws. 
6.  If tubed shelves were installed, place the tubes in place in the shelf brackets. 
7.  If sloped enclosures were ordered (for flue-mounted salamander broilers and/or cheese melters), install them at 
this time. 
S
TEP 
6:
 
C
ONNECT 
E
LECTRICITY 
(
FOR 
S
ECTIONS WITH 
O
VEN
-B
ASES
A wiring diagram is located behind the kick panel of the oven-base ranges. Be sure that the input voltage and phase 
match the requirements shown on the serial plate. 
Oven-base ranges ordered with a 115V, 60Hz, single-phase electrical rating are factory-supplied with one or two 
three-wire cords (one for each oven), each with a three-prong plug that fits any standard three-prong grounded 
receptacle. Each standard oven requires a 15 ampere supply, while each convection oven requires a 20 ampere 
supply. 
Oven-base ranges ordered with a 208/236V, 60Hz, single- or three-phase electrical rating are factory-equipped with 
one or two two-pole terminal blocks (one for each oven), located behind cover plate(s) located on the rear of the unit. 
To connect the supply wires, remove the appropriate cover plate. Route the supply wires and the grounding wire 
through the strain relief fitting to the terminal block. Insert the supply wires, one each, into the two poles of the 
terminal block and tighten the screws. Insert the ground wire into the grounding lug and tighten the screw. Re-attach 
the cover plate. 
Three phase units are wired as above, using only two supply wires. The third wire is not used and must be properly 
terminated. 
All units are shipped wired as specified by factory order. Conversion between single-phase and three-phase can be 
accomplished by referring to phase loading and line amperes chart on wiring diagram for wire size and ampere 
requirements. 
S
TEP 
7:
 
C
ONNECT 
G
AS 
S
UPPLY
 
If the sectional range is being installed at over 2,000 feet altitude and that information was not specified when 
ordered, contact the appropriate authorized Blodgett Range Service Representative or the Blodgett Range Service 
Department. Failure to install with proper orifice sizing will result in poor performance and may void the warranty. 
The sectional range is design-certified for operation on natural or propane gases. The sectional range is shipped 
configured and adjusted for the type of gas specified by the purchaser, which is indicated on the serial plate (see 
Figure 1 on page 3). Connect the sectional range ONLY to the type of gas for which it is configured and adjusted. 
Minimum supply pressure is 7" W.C. for natural gas, 11" W.C. for propane. An external pressure regulator and shut off 
valve are provided. If using a flexible-hose gas connection, the I.D. of the hose must not be smaller than the 
connector on the sectional range, and must comply with ANSI Z21.69. Provide an adequate means of restraint to 
prevent undue strain on the gas connection. 
If applicable, the vent line from the gas pressure regulator shall be installed to the outdoors in accordance with local 
codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1, Natural Gas Installation 
Code, CAN/CGA-B149.1,
 or the Propane Installation Code CAN/CGA-B149.2, as applicable. 
An adequate gas supply is imperative. Undersized or low pressure lines will restrict the volume of gas required for 
satisfactory performance. Fluctuations of more than 25% on natural gas or 10% on propane gas will create problems 
and affect burner operating characteristics. A 1/8" pressure tap is located on the manifold to measure the manifold 
pressure. The supply line to the sectional range should be no smaller than the inside diameter of the pipe on the 
sectional range to which it is connected.