Datalog 
3
 - SMS Software Application Sheet
EUROPLEX APLEX 100 & 3GS Alarm Panel Control Software - Page 3 of 9
CORTECH DEVELOPMENTS LTD
/Continued - Connection To APLEX Panel
After all the connections have been made, switch on the Aplex panel and follow the normal cold start
procedure. The Engineers code must set up the Aplex for serial communication. Enter the Engineers
code followed by (left shift 8). Set the Data format as follows:-
Printer:
No
System ID:
1 (or the panel ID in a chain system)
Access Control:
31
Log Filter:
8191
Dial Mode:
0
Baud Rate:
4800 (or as set in APLEX.DAT file, see
below)
Data:
8 Data Bits, Parity=Yes
The Datalog can now be powered up and will configure the Aplex correctly.  If a communication error
is reported by the Datalog, check that the serial wiring is correct and preferably check using a RS232
LED patch box to observe the data signals.