2700-I ACC Wood Insert
8
 Chimney Systems
   
 D.  Masonry Chimney
  • Must meet minimum standards of NFPA 211.
  • Must have at least 5/8 inch (16mm) fireclay lining joined 
with  refractory  cement.      (Installations  into  a  clay  flue 
without a stainless steel liner may reduce draw which affects 
performance, will cause the glass to darken and produce 
excessive creosote).
  • 
The  masonry  wall  of  the  chimney,  if  brick  or  modular 
block, must be a minimum of 4 inches (102mm) nominal 
thickness.
  • 
A  chimney  of  rubble  stone  must  be  at  least  12  inches 
(05mm) thick.
  • Cross-sectional  area  shall  conform  to  NFPA  211-2006 
Section 12.4.5.1.
  • Should be lined with a 6 inch (152mm) stainless steel flue 
liner to improve performance and reduce creosote build-
up.
 
• 
An equivalent liner must be a listed chimney liner system 
or other approved material.
  • No dilution air is allowed to enter the chimney.
    1. 
Secure the fireplace damper in the open position.  If this 
cannot be accomplished, it will be necessary to remove 
the damper
 
 
    2. Seal damper area of chimney around chimney connector 
with a high temperature sealant or seal insert against 
the face of the fireplace.
    . Both methods must be removable and replaceable for 
cleaning and re-installation.
  • When possible, install an airtight clean-out door to the rear 
of the smoke shelf.
A.  Venting Systems
Chimney Connector:
It is also known as flue pipe or stove pipe.  It must be 
6  inches  (152mm)  minimum  diameter  stainless  steel 
connector pipe.
Chimney
:
The  chimney  can  be  new  or  existing,  masonry  or 
prefabricated  and  must  meet  the  following  minimum 
requirements as specified below.
WARNING! Risk of Fire!
Follow  venting  manufacturer’s  clearances  and 
instructions when installing venting system.
B.  Inspections
Existing chimneys should be inspected and cleaned by a 
qualified professional prior to installation.  The chimney 
must not have cracks, loose mortar or other signs of dete-
rioration and blockage.  Hearth & Home recommends a 
NFI or CSIA certified professional or a technician, under 
the direction of a certified professional, conduct a Level II 
inspection per NFPA 211.
Fire Risk
Inspection of Chimney:
•  Chimney must be in good condition.
•  Meets minimum standard of NFPA 211
•  Factory-built chimney must be 6 inch 
(152mm) UL10 HT.
WARNING
NOTICE:  Check  with  your  local  building  authorities 
and/or consult the National Fire Protection Association 
(NFPA 211).  
C.  Larger Chimneys
It  is  recommended  that  chimneys  with  larger  diameters 
than  6  inches  (152mm)  be  relined.    An  oversized  flue 
can  affect  draft  and  impair  performance  and  will  allow 
increased build-up of creosote.