2.4 AC POWER
The AC power source to the Johnson VIKING 
VX Repeater can be 120V AC or 240V AC.  Nothing 
need be done to the power supply for 240V AC opera-
tion.  However, a 240V AC outlet requires that the 
120V AC power plug be replaced.  A locking AC 
power cord is provided for the supply.
The 120V AC cord is a standard 3-wire grounded 
cord used with a standard AC wall outlet.  The outlet 
must be capable of supplying a minimum of 560W.  
With the nominal 120V AC input, the source must 
supply 5A for each 110W repeater and should be pro-
tected by a circuit breaker.  It is recommended that all 
of the repeaters in a rack should not be on the same 
breaker in order to provide one operational repeater in 
the event a breaker trips.  An AC surge protector is 
recommended for all equipment.
Each Repeater requires an outlet, so for a 5-chan-
nel system, a minimum of 5 outlets is required.  An 
additional three outlets should be added for test equip-
ment.  The outlets must be within 3 feet of each 
Repeater cabinet.  Future system expansion should be 
considered when electrical work is being planned for 
the initial system.
The VIKING VX Repeater power supply can be 
equipped with an optional 24V DC back-up in the 
event of AC power failure.  Since the transmitter will 
remain on full power, if desired, the DC power source 
must have a current capability of about 20A per 110W 
repeater or 100A for 5 - 110W repeaters.  The multi-
coupler requires another 0.5A for a total system 
requirement at 24V DC of 100.5A for 110W repeaters.
2.5 BATTERY BACKUP
If the power supply is equipped with battery 
backup, screw lugs are provided on the front of the 
power supply for battery connections (see Figure 2-1).  
A switch is provided for charging the battery or can be 
off if a separate battery charger is used.  A battery 
temperature sensor connection is also provided.  The 
temperature sensor cable is shown in Figure 2-2.  LED 
indicators are provided to show Reverse Battery con-
nection, Charger On/Off and Battery Fault.
Figure 2-1   BATTERY BACKUP CONNECTOR
The temperature sensor is required to adjust the 
charging voltage over temperature.
Figure 2-2   TEMPERATURE SENSOR CABLE
2.6 800W POWER SUPPLY
The power supply has four voltage output levels 
(see Table 2-1).  Each voltage is set to ±1% at +25°C 
(+77°F).  The output of this supply is capable or run-
ning any 2000 series repeater.  
Each output is overload protected such that the 
power supply current limits and automatically resets 
when the overload is removed (see Table 2-1).  
Each output is over voltage protected such that 
the power supply shuts down when an over voltage 
condition exists, usually when a component in the 
supply has failed (see Table 2-2).  The power supply 
must be manually reset by toggling the Enable Line or 
removing AC power for more than 10 seconds.
B-
B+
TEMP
ACTIVE
CHARGER
ON
CHARGER
FAULT
BATTERY
BATTERY
REVERSE
GROUND
EARTH
NEUTRAL
LINE
SWITCH
BATTERY
TEMP
TERMINAL
NEGATIVE
GND
BLK
WHT