Insulation Resistance Measurement – M
Ω
@UISO
 Function
5.7.1 Preparing for Measurement
Note

Testing the Measurement Cables 
The test probes at the ends of the measurement cables 
should be short circuited before performing insulation 
resistance measurements with the selector switch in the 
Ω 
or the 
 position, in order to make sure that a value close 
to 0 
Ω is displayed at the instrument. Incorrect connection or 
a broken measurement cable can be detected in this way.
Note

Insulation resistance may only be measured at voltage-free 
devices. The measurement cables may not come into con-
tact with one another during high-resistance insulation 
measurements.
➭ Set the rotary switch to “
M
Ω
@UISO
”.
➭ Connect the measurement cables to the two accessible jacks.
➭ Interference voltage measurement (V AC+DC TRMS) is 
conducted in this switch position.
The FUNC | ENTER key for U
ISO
 ON / OFF may only be pressed 
in order to start the insulation resistance measurement if the 
device under test is voltage-free. 
Note

The M
Ω
@UISO
 switch position may only be used for 
insulation resistance measurement. However, if interference 
voltage is inadvertently applied with the switch in this 
position, it appears at the display.
If an interference voltage of 
> 50 V is present, insulation 
resistance measurement is disabled. The LCD continues to 
display the interference voltage value. If a voltage of greater 
than 1000 V is present, an acoustic signal is generated as 
well.
COM mA A
V
Temp
Ω MΩ
ISO
00.00
Ω
Short circuit the measurement cables.
R
x
0 V  !
!
Ω
M
Ω
@UISO
V
Interference Voltage Detection
000.0
V
DC
AC
TRMS
1M
Ω
ISO 500 V