Measurements: V/Hz, 
Ω,  , Temp (°C/°F), 
, M
Ω
@UISO
, A/Hz
Caution: High-Voltage!
Do not touch the conductive ends of the test probes when the 
instrument has been activated for the measurement of insulation 
resistance. 
You may otherwise be exposed to a current of 2.5 mA 
(limited in the measuring instrument), and although this is 
not life endangering, the resulting electrical shock is quite 
discernible. 
If, on the other hand, measurement is being performed on a 
capacitive device under test, for example a cable, it may be 
charged with up to approximately 
±1200 V.
Touching the device under test after measurement has been 
performed is life endangering in this case!
Selecting the Test Voltage (U
ISO
 = 50 to 1000 V)
The desired test voltage can be selected in the “
SET” menu (see 
 
1nFo 
Z
 ... 
Z
 
SET 
 
rAtE 
V
 ... 
V
 
v1so
 ... 
500, 1000 V* 
UV
 
 
* Selectable test voltages and the default value depend upon the 
respective device variant.
The selected test voltage appears at the display during testing.
5.7.2 Performing the Insulation Measurement
➭ Starting the insulation resistance measurement: 
Press and hold the U
ISO
 ON / OFF key until the display settles 
in, in order to measure insulation resistance. 
Insulation resistance measurement is ended by releasing the 
key.
Auto-ranging is active during insulation resistance measurement. 