9. Conducting tests in accordance with DIN VDE 0701 and
DIN VDE 0702:
Definition of standards
The sequence of tests is specified in the standard:
9.1 Visual inspection
The test objects are inspected for externally visible defects.
9.2 Measuring the protective conductor resistance
(with devices of protection class I)
The limit value is:
0.3  
Ω
Ω
Ω
Ω
Ω for devices with connecting cables up to 5 m,
plus 0.1 
Ω for every 7.5 m, but a mximum of 1.0 Ω.
9.3 Measuring insulation resistance
The limit value is:
1 M
Ω
Ω
Ω
Ω
Ω for devices of protection class I
2 MΩ
Ω
Ω
Ω
Ω ffor devices of protection class II 
1)
0.25 MΩ
Ω
Ω
Ω
Ω for devices of protection class III
0.3 MΩ
Ω
Ω
Ω
Ω for devices of protection class I
with switched-on heating elements 
2)
1)
Also applies for touchable conductive parts of test objects in
protection class I  that are not  connected to the protective conductor.
2)
If the required insulation resistance is not achieved in the case of  test objects in
protection class I with heating elements with a total capacity 
 3.5 kW, the test object
is nevertheless rated as faultless if  the protective conductor current does not exceed
the limit values.
Measuring principle circuit
protective conductor resistance PC I, Diagram M1
Tester
Test  object
Test  line
Measuring principle circuit
Insulation resistance PC I, Diagram M2
PC II and III, Diagram M3
Tester
Test
object
Test line
&
&
&
&
&
If the insulation measurement is technically impossible, then a
protective conductor current measurement (direct or differential
current method) must be carried out on test objects in PC I and a
touch current measurement on test objects in PC II.
17
Operating manual for the TG uni 1 appliance tester
Conducting tests in accordance with VDE 0701 and 0702 - definition of standards
´Probe´
 socket
Test socket
Test line
Test socket
Test  socket
´Probe´
socket
´Probe´
socket