Utica Boilers UB90-200 Installationsanweisungen

Seite von 50
17
Connections And Termination
Installation must conform to requirements of authority 
having jurisdiction or, in absence of such requirements, 
to the section for Air for Combustion and Ventilation of 
the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/
or Natural Gas and Propane Installation Code, CAN/CSA 
B149.1.
Installer must clean and remove all shavings from interior 
of all pipes used on air intake to prevent damage to gas 
burner and ensure proper operation.
Boilers require dedicated direct vent system. All air for 
combustion is taken directly from outdoors through 
combustion air intake pipe. All flue products are discharged 
to outdoors through vent pipe.  Install vent system in 
accordance with instructions in this manual.
1. 
Figures 8 and 9 “Combustion Air and Vent Pipe 
Requirements, for standard two-pipe roof and sidewall 
terminations and Figures 10, 11, and 12 for concentric 
vent terminations (roof termination is preferred). 
Combustion air and vent pipes must terminate together in 
same atmospheric pressure zone as shown. Construction 
through which vent and air intake pipes may be installed 
is minimum ¼” and maximum 24” thickness.
2. 
Combustion air and vent pipe fittings must conform 
to one of the following American National Standards 
Institute (ANSI) and American Society for Testing and 
Materials (ASTM) standards:
3. 
Combustion air and vent piping connections on boiler 
are 2”, but must increase to 3”. Due to potential for 
flue gas temperatures over 155°F, first 5 feet of vent 
pipe must be CPVC (furnished), remaining vent pipe 
can be PVC. This requirement is not required when 
using PP. If any elbows are employed within first 2½’ 
of vent, they must be CPVC. Two 30” pieces of 2” CPVC 
pipe and one 2” CPVC coupling are furnished with 
boiler. See Figure 13.
Length of pipe is counted from boiler jacket (air intake 
pipe) or from vent tee (vent pipe). First five feet of “Total 
Equivalent Length” of vent pipe must be CPVC.  This 
requirement is required when using PP.
Reduce maximum vent length 5 feet per each additional 
elbow.
4. 
Pitch horizontal combustion air and vent piping back 
to boiler at minimum ¼” per foot (21mm/m) from 
intake and vent terminals so all moisture in combustion 
air and vent piping drains to boiler. Pitch pipes 
continuously with no sags or low spots where moisture 
can accumulate and block flow of air or flue gas. This 
blockage may cause combustion instability, noise and 
lead to nuisance control lockouts.
5. 
Combustion air and vent pipes must be airtight, 
watertight and tested for leaks.
7 - COMBUSTION AIR AND VENT PIPE
WARNING
Use of cellular core PVC (ASTM F891), cellular core 
CPVC, or Radel
®
 (polypenolsulfone) in venting 
system could result in death, serious injury.
!
  
Table 6  Combustion Air and Vent Pipe 
Length Requirement
3 in. Pipe
Minimum Venting
* 3 in. Pipe
Maximum Venting
6 ft. (1.8 m) in length
60 ft. (18.3 m) in length and 
up to four (4) 90° elbows  
1 - 90° elbow = 5 ft (1.6 m)
1 - 45° elbow = 3.5 ft (1.1 m)
1- 2” x 3” adapter = 0 ft (0 m)
   All field installed vent pipe must be 3”
* Past first 2” section provided with boiler