Utica Boilers UB90-200 Installationsanweisungen

Seite von 50
15
If concentric vent termination is being used, refer to 
Figure 10 for proper setup.
6 - COMBUSTION AIR/ VENT REQUIREMENTS
Figure 9  - Multiple Boiler Roof Vent/Intake 
Terminations
Figure 10 -  Sidewall Vent/Intake Terminations
Combustion Air/Vent Pipe Requirements
Boiler requires dedicated direct vent system. Direct vent 
system, all air for combustion is taken directly from outside 
atmosphere, and all flue products are discharged to outside 
atmosphere. 
Combustion air and vent pipe connections must terminate 
together in same atmospheric pressure zone, either 
through roof or sidewall (roof termination preferred). See 
Figures 8 and 9 for required clearances.
Venting must be as direct as possible and properly 
supported.
12" (305mm) 
Minimum
8" (203mm)
Minimum
15" (381mm) 
Maximum
3" (76mm) 
Minimum
Vent
Combustion 
Air
12" (305mm) 
Minimum Above 
Anticipated Snow Line
Vent
3" (76mm) 
Minimum 
Separation
12" (305mm) 
 
Minimum From 
Overhan
g
12" (305mm) Separation 
Between Bottom of 
Combustion Air Intake 
And Bottom of Vent
See Snow & 
Ice Page 19
Combustion Air
Vent
12" (305mm) 
Minimum 
Separation
Combustion Air
Figure 11 - Concentric Vent Terminations
Combustion Air
1" (26mm) 
Maximum
Maintain 12"
 clearance above 
highest anticipated 
snow level or grade
* See Note 
Below
36"(0.9m) Minimum
Maintain 12"(305mm) 
Clearance Above Highest 
Anticipated Snow Level 
or Grade
Canada see page 19
12" (305mm) Minimum
*Must be less than 4" or greater than 24" Horizontal distance 
between end bells of each air intake to prevent flue gas recirculation.
Overhang
• Avoid locations where 
snow may drift and block 
vent and combustion air. 
• Ice or snow may cause 
boiler to shut down if 
vent or combustion air 
becomes obstructed.
Vent
Combustion Air
Vent
Single Boiler 
Application
Multiple Boiler 
Application
Single Boiler 
Application
Multiple Boiler 
Application