Utica Boilers UB90-200 Installationsanweisungen

Seite von 50
26
See “Troubleshooting” on page 31 for detailed sequences of 
operation and troubleshooting procedures. See separately 
provided “Repair Parts Manual” for locations of control 
components and accessories described.
Integrated Boiler Control (IBC)
• Integrated Boiler Control (IBC) is a microprocessor 
based controller for high efficiency gas boilers. 
• Controller monitors all safety controls which control 
operation of combustion air blower, circulator pump, 
burner, and combination hot surface igniter/flame 
sensor. 
• Controller is not intended for use with vent damper. 
Controller is mounted on control panel inside boiler. 
Contains five diagnostic indicator lights.
Gas Control Valve
Electronic 24 volt gas control valve contains 1:1 gas/air 
pressure regulator, controls gas flow to main burner of 
appliance. Suited for both natural and LP gas, and rated in 
accordance with ANSI Z21.21 - latest revision and CGA-
6.5-M95. 
Hot Surface Igniter
• 120 volt hot surface igniter heats up 1800°F initiates 
combustion of gas in burner.
• Igniter is mounted next to burner through gas/air mixer. 
• Igniter also serves as means for proving main burner 
flame by flame rectification. 
A.  In event of lack of flame signal on three consecutive 
trials for ignition, IBC will lock out. 
B.  “Valve” and “Flame” diagnostic indicator lamps blink 
indicating failure mode as lack of flame signal. 
C.  Manually reset IBC from lockout by removing and 
re-establishing thermostat’s call for heat, or turn 
service switch off, then back on.  See Figure 19.
High Limit Control
NOTICE
Maximum set-point of limit control must not exceed  
190°F.
• High limit control determines maximum boiler water 
temperature and provides means for protecting boiler 
and heating system from unsafe operating conditions 
which could damage boiler. 
• Control is mounted in ½” NPT control well and ¾” x ½” 
bushing on top of front boiler section at hot water outlet. 
• Control is tied in with IBC and factory set at 190°F water 
temperature. 
• High limit set-point is field adjustable and may be set 
between 100°F and 190°F. 
• Field set-point adjustment for each installation depends 
on heating system requirements. 
• Differentials are automatic, vary based on control 
settings and boiler temperature.
• Refer to limit manufacturer instructions provided with 
limit control.
Casting Temperature Safety Switch
NOTICE
Never run cold water into hot, empty boiler.
Casting temperature safety switch (230°F set-point) shuts 
off boiler by shutting off power to IBC, result of lack or loss 
of boiler water. Power indicator light goes out. 
Switch is installed on top of aluminum boiler section behind 
supply piping.
Fault requires manual reset of casting temperature safety 
switch, restarting boiler. Verify boiler is filled with water 
before resetting switch.
10 - CONTROLS AND ACCESSORIES
Figure 19 - Gas Valve
Figure 20 - Indicator Lights