Initial Service Checks
1. 
Before Troubleshooting:
A.  Verify circuit breaker is on or fuse is OK at electrical 
panel.
B.  Verify service switch is ON.
C.  Verify Gas is ON at:
•  Gas meter 
•  Appropriate manual shutoff valves
•  Gas control valve
D.  Verify thermostat is calling for heat.
E.  Verify wire connections at integrated boiler control 
(IBC) and originating control are securely plugged 
in or connected. 
F.  Check hoses are securely connected and are not 
plugged or damaged.
2. 
Troubleshooting Tools:
A.  Voltmeter to verify 120 VAC and 24 VAC
B.  Continuity Tester
C.  Inclined Manometer or Pressure Gauge with 0-2.0” 
range (0.01” scale) for measuring suction pressures 
at pressure switch. 
D.  U-Tube Manometer or Differential Pressure Gauge 
with 0-14” range (0.1” scale) for measuring inlet 
and manifold gas pressures.
3. 
System Status:
A.  Consult “System Status” on page 40.
B.  See Figure 19, Page 26, for location of boiler 
Diagnostic Indicator Lamps.
15 - TROUBLESHOOTING
 WARNING
Fire, explosion or shock hazard may cause death or 
serious injury. Do not attempt to modify physical or 
electrical characteristics of this boiler in any way.
!
  
•  In reset from lockout condition, all electrical meter 
readings at gas control valve (24 vac) must be taken 
within trial for ignition period. 
•  If any component dose not function properly, make 
sure it is correctly installed and wired before replacing.
•  Static electricity discharge can damage integrated 
boiler control (IBC).  Touch metal surface to discharge 
static electricity before touching IBC.
•  IBC cannot be repaired.  If it malfunctions it must be 
replaced.
•  Only trained, experienced  service  technicians should 
service IBC systems. Follow troubleshooting to check 
out system and sequence of operation for normal light 
off sequence.
•  Defective control is least likely cause of malfunction. 
If you suspect unit has defective control, read through 
troubleshooting chart before replacing it. 
•  It is unlikely two consecutive controls are defective. If 
this seems to be the case chances are the controls are 
not the cause but rather malfunction is due to some 
other problem such as electrical short burning out 
transformer.