Utica Boilers UB90-200 Installationsanweisungen

Seite von 50
38
15 - TROUBLESHOOTING
High Limit Control and LWCO 
LED Legend and LWCO Test Button
1
 HI TEMP illuminates when boiler water temperature 
reaches high limit setting. Remains lit until water 
temperature falls 10°F. Limit prevents burner operation 
while this LED is on.
2
 LWCO ACTIVE Indicates low water cut-off function is 
active. When control is installed with Electro-well, LED is 
on at all times when control is powered. If the control is 
installed with a well other than Electro-well, LED will not 
illuminate indicating the control is not providing low water 
cutoff functionality.
 WARNING
Burn and scald hazard. Do not add water until boiler 
has fully cooled. Failure to follow these instructions 
could result in death or serious injury.
!
  
3
 LWCO  LOW WATER Illuminates if boiler is in low water 
condition. Control will prevent burner operation during this 
condition.  
Important: System must be checked by qualified service 
agency prior to resuming operation.
4
 ECONOMY  ACTIVE Indicates that thermal targeting 
function is active and control reduces boiler temperature 
to conserve fuel.  Economy feature is activated using the 
ECONOMY dial. 
  
5
 
ECONOMY  TARGET  When feature is active, control 
continually sets target temperatures below high limit 
setting to maximize fuel efficiency. When boiler reaches 
target temperature, LED illuminates  and burner shuts 
down.  Boiler water continues to circulate and het the 
house as long as thermostat call continues.  LED stays lit 
until boiler temperature drops below differential at which 
point boiler will be allowed to fire again. 
Note: LED illuminates regularly during normal boiler 
operation.
6
  
PURGE Control is purging latent heat from boiler and 
will not fire until temperature drops to 135°F. 
7
LWCO To Test LWCO: Press and hold TEST button. Red 
Low Water light will illuminate and burner circuit will de-
energize.
  
Figure 21 - LED Legend