Hamilton Sundstrand Company Fuel Metering Valves XVG Benutzerhandbuch

Seite von 36
 
 
 
8.1  RS-232 Connection (for XVG/eXVG with RS-232 interface) 
 
PC COM Port 
(DB9M Connector) 
XVG/eXVG Terminal 
Block 
Wire Color 
(If XVG/eXVG is 
supplied with optional 
harness) 
Signal 
Pin # 
Signal 
Pin # 
 
SERIAL RX 
SERIAL TX 
39 
WHT/ORN/BLU 
SERIAL TX 
SERIAL RX 
40 
WHT/ORN/YEL 
SERIAL RTN 
SERIAL RTN
41 
WHT/ORN/GRN 
Table 14:  RS-232 Interface Connection 
 
8.2  RS-485 Connection (for XVG/eXVG with RS-485 interface) 
 
PC COM Port 
Through RS232-
RS485 Converter 
XVG/eXVG Terminal 
Block 
Pin # 
Signal 
Pin # 
Wire Color 
(If XVG/eXVG is supplied 
with optional harness) 
TD(B)+ 
TXD-485A  
(SERIAL TX) 
39 WHT/ORN/BLU 
TD(A)- 
RXD-485B  
(SERIAL RX) 
40 WHT/ORN/YEL 
GND (Optional) 
SERIAL RTN 
41 
WHT/ORN/GRN 
Table 15:  RS-485 Interface Connection 
XVG/eXVG Modbus Parameters 
 
9.1  Setup Parameters 
 
Set up parameters are write-able parameters used to setup and control all XVG/eXVG 
operations.  The following notes applied to all parameters: 
 
-  Register Number:  This is the Modbus address of the register in the XVG/eXVG.   
-  All registers are readable.   
-  RO:  Read-only.  The register is read-only.  
-  W0:  Open access for writing by any user. 
-  W1:  A Customer or Factory level password must be entered before writing is 
allowed. 
-  W2:  A password must be entered and IDM_SETUPCONNECT (register no. 
3005) set to 1 before writing is allowed. 
-  W3:  A factory level password must be entered before writing is allowed. 
-  W4:  A factory level password must be entered and IDM_SETUPCONNECT set 
to 1 before writing is allowed. 
 11