9.1.1  General Setup Parameters 
 
Register 
Number 
XVG/eXVG Parameter 
Name 
Write 
Access 
Description Type 
Default 
Value 
3500 IDM_MODE 
W2 
Operating Mode: 0=Stroke, 1=Flow 
Measurement, 2=Flow Control, 3=Flow 
Limiting 
U16 0 
3501 IDM_PROTOCOL 
W2 
Bit15=Don’t care, Bit14 = inter-character 
timeout enable for Modbus, other bits 
reserved 
U16
 
3502 
IDM_DEMANDSRC 
W4 
Demand Source, not used
 
U16 0 
3503 IDM_DIGCMDEN 
W4
 
Digital Command Enable: Bit0, 0=Analog, 
1=Digital, other bits reserved 
U16
 
3504 IDM_SOLMAXAMPS 
W4
 
XView functional flag: 1= XView will allow 
parameter download to valve regardless of 
demand signal, 2=XView will not download 
if Demand>3% (2 is for Solar OEM units) 
U16
 
3505 IDM_CURVOLTCFG 
W4
 
Current/Voltage Select: Bit0-Bit5=AI0-AI5, 
Bit8-Bit10=AO0-AO2, 0=Current, 1=Voltage 
U16
 
63 
3506 IDM_DEMANDOFFST 
W4
 
Demand Offset: ADC counts, range 0-956 
U16
 
683 
3507 IDM_POSINTTBLEN 
W4
 
Position Interpolation Table Enable: 
0=Disable, 1=Enable 
U16
 
3508 IDM_LVDTPHASE 
W4
 
LVDT phase: Range 0-32 
U16
 
3509 IDM_AOPOLARITY 
W4
 
Analog Output Polarity: Bit0-Bit2=AO0-
AO2, 0=Positive, 1=Negative 
U16
 
3510 IDM_MINDEMAND 
W4
 
=700 if IDM_MODE = 0, 1 or 2,  
=600 if IDM_MODE = 3,  
Range 600-4000, default represents 4.1mA  
U16
 
700 
3511 IDM_VERSION 
W4
 
Valve Type Identifier:  
2=Flow Limiting 
Mode (Enabled At Factory). 
 
1=Non Flow Limiting 
U16
 
3512 
IDM_CONFIGNO 
W4 
Configuration Number: Range 0-65535
 
U16 102
 
3513 IDM_VOLTRANGE 
W4
 
I/O Volt Range, Bit format same as 
IDM_CURVOLTCFG, 0=0-5V, 1=1-5V/4-
20mA 
U16
 
3514 IDM_FLTTM3VOLT3 
W4
 
3.3V fault persist time:  x20mS, range 0-
32767 
U16
 
3515 IDM_FLTTMINPRES 
W4
 
Input pressure fault persist time:  x20mS, 
range 0-32767 
U16
 
3516 IDM_FLTTMOUTPRES  W4
 
Output pressure fault persist time:  x20mS, 
range 0-32767 
U16
 
3517 IDM_FLTTMLVDT 
W4
 
LVDT fault persist time:  x20mS, range 0-
32767 
U16
 
3518 IDM_FLTTMTRACK 
W4
 
Tracking fault persist time:  x20mS, range 0-
32767 
U16
 
50 
3519 IDM_FLTTMGASTEMP  W4
 
Gas Temp fault persist time:  x20mS, range 
0-32767 
U16
 
50 
3520 IDM_FLTTMOVRPRES  W4
 
Overpressure fault persist time:  x20mS, 
range 0-32767 
U16
 
 12