7 - NEAR BOILER PIPING
7.3 Safety Relief Valve / Temperature Pressure Gauge
 WARNING
Burn and scald hazard.  Safety relief valve could       
discharge steam or hot water during operation.       
Install discharge piping per these instructions.
!
     
Installation of (supplied) safety relief valve shall conform to 
ANSI/ASME Boiler and Pressure Vessel Code, Section IV.  
• Install furnished safety relief valve using 3/4” pipe 
fittings provided with boiler. See Figure 2.
• Install safety relief valve with spindle in vertical 
position.
• Do not install shutoff valve between boiler and safety 
relief valve.
• Install discharge piping from safety relief valve.  See 
Figure 2.
• Use ¾” or larger pipe.
• Use pipe suitable for temperatures of 375°F (191°C) or 
greater.
• Individual boiler discharge piping shall be independent 
of other discharge piping.
• Size and arrange discharge piping to avoid reducing 
safety relief valve relieving capacity below minimum 
relief valve capacity stated on rating plate.
• Run pipe as short and straight as possible to location 
protecting user from scalding.
• Install union, if used, close to safety relief valve outlet.
• Install elbow(s), if used, close to safety relief valve 
outlet and downstream of union (if used).
• Terminate pipe with plain end (not threaded).
7.4 Expansion Tank & Make-up Water
• Determine required system fill pressure, system design 
temperature, and system water content. 
• Boiler contains 2.6 gallons (US). Size expansion tank 
accordingly. 
• Consult expansion tank manufacturer for proper sizing 
information. Connect properly sized expansion tank 
(not furnished) as shown in
 
Figure 3 for diaphragm 
type expansion tank. 
• Adjust tank air pressure on diaphragm type expansion 
tanks to match system fill pressure. 
• Install air vent (furnished) as shown for diaphragm 
type expansion tank system only.
• Install make-up water connections as show. 
• If pressure reducing valve is used, adjust to match 
system fill pressure. 
• Verify clean water supply is available when connecting 
cold make-up water supply to boiler. 
• Use sand strainer at pump if water supply is from well 
or pump.
GATE VALVE
REDUCED PRESSURE 
BACKFLOW PREVENTER
FEED 
WATER
PRESSURE 
REDUCING VALVE
AIR SCOOP
DIAPHRAGM TYPE
EXPANSION TANK
SUPPLY PIPING
Check local codes 
for maximum 
distance from 
floor.
FLOOR
Safety Relief Valve
Figure 2 -  Safety Relief Valve Discharge Piping
Figure 3  - Diaphragm Type Expansion Tank Piping
10