Utica Boilers UB95M-200 Installationsanweisungen

Seite von 52
6.2 Combustion Air and Vent Pipe Requirements
• This boiler requires dedicated direct vent system. 
• In direct vent system all air for combustion is taken 
directly from outside atmosphere, and all flue products 
are discharged to outside atmosphere.
• Combustion air and vent pipe connections must 
terminate together in same atmospheric pressure 
zone, either through roof or sidewall (roof termination 
preferred). See Figures 5 and 6
 
for required clearances. 
For proper set up of concentric vent termination see 
Figure 7 and Figure 8.
 WARNING
Solvent cements are combustible. Keep away from 
heat, sparks, and open flame. Use only in well 
ventilated areas. Avoid breathing in vapor or allowing 
contact with skin or eyes. Failure these instructions 
could result in fire, personal injury, or death.
!
  
• Locate combustion air inlet as far away as possible 
from swimming pool and swimming pool pump house. 
• All combustion air and vent pipes must be airtight and 
watertight. Combustion air and vent piping must also 
terminate as shown in “Combustion Air and Vent Pipe” 
section.
• Vent connections serving appliances vented by 
natural draft shall not be connected into any portion 
of mechanical draft systems operating under positive 
pressure.
• Covering non-metallic vent pipe and fittings with 
thermal insulation shall be prohibited.
6 - LOCATING THE BOILER
6.3 Condensate Drain Requirements
• Condensate trap provided with boiler, an additional 
trap is not required and should not be used.
• Pitch condensate drain line down to floor drain at 
minimum of ¼” per foot. External condensate pump 
(not furnished) may be used if floor drain is not 
available. 
• Condensate pump must be designed for flue gas 
condensate application.
• Wood frame or blocks may be used to raise boiler 
to maintain drain pitch or to be above external 
condensate pump reservoir.
• If boiler is not level, condensate drain lines will not 
function properly.  Adjustable feet are located on boiler 
to make up for minor surface irregularities or tilt.
• 115 volt AC receptacle provided on control panel to 
provide power for external condensate pump if used.
6.4  Removal of Existing Boiler From Common 
Vent System
When an existing boiler is removed from a common 
venting system, the common venting system is likely to be 
too large for proper venting of the appliances remaining 
connected to it. At the time of removal of an existing boiler, 
the following steps shall be followed with each appliance 
remaining connected to the common venting system 
placed in operation, while the other appliances remaining 
connected to the common venting system are not in 
operation.
1. 
Seal any unused openings in the common venting 
system.
2. 
Visually inspect the venting system for proper size and 
horizontal pitch and determine there is no blockage, or 
restrictions, leakage, corrosion and other deficiencies 
which could cause an unsafe condition.
3. 
In-so-far as is practical, close all building doors and 
windows and all doors between the space in which the 
appliances remaining connected to the common venting 
system are located and other spaces of the building. 
Turn on clothes dryer and any appliance not connected 
to the common venting system. Turn on any exhaust 
fans, such as range hoods and bathroom exhaust, so 
they will operate at maximum speed. Do not operate a 
summer exhaust fan. Close fire dampers. 
4. 
Place in operation the appliance being inspected. 
Follow the lighting instructions. Adjust thermostat so 
appliances will operate continuously.
5. 
Test for spillage at the draft hood relief opening after 5 
minutes of main burner operation. Use the flame of a 
match or candle, or the smoke from a cigarette, cigar 
or pipe.
6. 
After it has been determined that each appliance 
remaining connected to the common venting system 
properly vents when tested as outlined above, return 
doors, windows, exhaust fans, fire place dampers, 
and any other gas-burning appliance to their previous 
condition of use.
7. 
Any improper operation of the common venting system 
should be corrected so the installation conforms with 
the National Fuel Code, NFPA-54/ANSI -Z223.1 and/or 
the Natural Gas and Propane Installation Code, CAN/
CSA B149.1. When re-sizing any portion of common 
venting system, common venting system should be re-
sized to approach minimum size as determined using 
appropriate tables in Chapter 13 of the National Fuel 
Gas Code, NFPA-54/ANSI- Z223.1 and/or the Natural 
Gas and Propane Installation Code, CAN/CSA B149.1.
8