Chapter 4: Operation 
29 of 50 
Programming Mode 
The motor will stop when in Programming mode. 
1.  Make sure DIP switches 1 through 4 and 7 and 8 are OFF
2.  Flip switch 7 to ON. 
3.  The display should read PROG. 
4.  Follow the instructions given below to view and/or edit any of the variables. 
Viewing or Changing Displayed Decimal Place/Rate or Time Mode Select 
1.  Make sure you are in Programming Mode, then flip DIP switch 4, RATE-TME 
MODE/PROGRAM DECIMAL PLACE, ON. 
2.  The current decimal point setting, if any, FACTORY SETTING = 0, will be 
displayed. 
3.  Use the Up or Down buttons to change the decimal point as desired.  Use for NO 
decimal point. 
4.  When finished, flip DIP switch 4 to OFF. 
5.  The display should read PROG (the decimal point, if any, is also displayed). 
Viewing or Changing the Constant 
1.  Calculate the constant for your application using the formula listed on the previous 
page. 
2.  Make sure you are in Programming Mode, then flip DIP switch 1, PROGRAM 
CONSTANT, to ON
3.  The current value for the constant, FACTORY SETTING = 30, should not be 
visible on the LED display. 
4.  Use the Up or Down buttons to adjust the constant value. 
5.  When finished, flip DIP switch 1 to OFF. 
6.  The display should read PROG. 
The display setting is set to the slowest speed when you exit the Programming Mode. 
Programming for Follower Operation 
1.  Enter Programming Mode, then turn DIP switches 5, MASTER/FOLLOWER 
SELECT, and 1, PROGRAM CONSTANT, to ON. 
2.  Set constant to: 
CONSTANT = 1000 x PULSES PER REVOLUTION OF MASTER 
 
 
 
   PULSES PER REVOLUTION OF FOLLOWER = 30.0 
 
3.  Turn OFF switches 1 and 7. 
4.  Turn OFF AC power, then reapply AC power.  The control is now set for follower 
operation.