Additive Feeders 
Chapter 4: Operation 
30 of 50 
Viewing or Changing the Program Minimum Setting 
1.  Enter the programming mode, then flip DIP switch 2, Program Minimum Setting, 
to ON. 
2.  The current value for the lower limit FACTORY SETTING = 0 will appear in the 
LED display. 
3.  Use the Up or Down buttons to change the lower limit, as desired. 
4.  When finished, flip DIP switch 2 to OFF. 
5.  The display should read PROG. 
Viewing or Changing the Program Maximum Setting 
1.  Enter the programming mode, then flip DIP switch 3, PROGRAM MAXIMUM 
SETTING to ON. 
2.  The current value for the upper limit FACTORY SETTING = 70 will appear in the 
LED display. 
3.  Use the Up or Down buttons to change the upper limit, as desired. 
4.  When finished, flip DIP switch 3 to OFF. 
5.  The display should read PROG. 
Exiting Programming Mode and Returning to Run Mode 
1.  Make sure DIP switches 4, TIME/RATE MODE SELECT, and 5, 
MASTER/FOLLOWER MODE SELECT are in the desired positions factory 
Setting 4 = 1, 5 = OFF, ON FOR OPTIONAL EXTRUDER TRACKER 
CONTROLS BEFORE 
entering the RUN mode (DIP switch 7 OFF). 
2.  Make sure DIP switches 1 through 4 are OFF
3.  If satisfied with the programmed values, flip DIP switch 7 to OFF. 
4.  Control should begin to operate normally, using the values and modes selected. 
Figure 3:  DIP Switch Function Table 
Switch 1 
Program Constant 
 
Switch 2 
Program Minimum Setting 
 
Switch 3 
Program Maximum Setting 
 
Switch 4 
Decimal Select 
0 – 4 = Decimal Points 
Switch 5 
Master/Follower Select 
OFF = Master  ON = Follower 
Switch 6 
Do Not Use – Set to OFF 
 
Switch 7 
Program/Run Select 
OFF = Run  ON = Program 
Switch 8 
Do Not Use – Set to OFF