Toshiba Tortilla Maker HV6FS-MLD Installationsanweisungen

Seite von 38
 
 
GENERAL DESCRIPTION 
Page 9 
 
 
 
INDICATORS AND CONTROLS (Fig. 4) 
 
The following front panel indicators and controls 
are provided: 
 
1) 
 On-Off Indicator - Indicates if the circuit 
breaker is OFF (Green)  or ON (Red).  When 
the indicator reads OFF, the main contacts of 
the circuit breaker are open.  When the 
indication is ON, the main contacts are 
closed. 
 
2)   Closing Spring Status Indicator - Indicates if 
the closing springs are CHARGED (Yellow) 
or DISCHARGED (White). 
 
3)  Manual Charging Handle – Turn the handle 
clockwise 3 to 5 times will charge the closing 
spring. (Closing Spring Status Indicator 
changes to CHARGED, Yellow)  When the 
handle is released, it returns to its normal 
position, and do not attempt to turn again. 
 
4)  Manual Close Lever (Green) - Pushing the 
lever in the direction of the arrow closes the 
circuit breaker (On-Off indicator changes to 
ON). 
 
5)   Manual Trip Lever (Red) – Pushing the lever 
in the direction of the arrow trips the circuit 
breaker (On-Off indicator changes to OFF). 
 
6) 
 Operations Counter - Indicates the total 
accumulated number of times the circuit 
breaker has been closed. 
 
 
 
 
 
 
 
 
Fig. 4  Indicators and Controls 
 
 
 
 
 
 
 
 
1
2
3
4
5
6
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net