INSTALLATION 
 
 
 
PLACING THE CIRCUIT BREAKER IN THE 
CELL
 
 
Hazard of fire, explosion, 
severe injury, death and 
property damage.  Circuit 
breaker must be OFF 
before installation or 
removal from cell. 
 
Circuit breaker contains 
powerful springs.  
Discharge springs 
completely before 
installation or servicing.
 
 
Before attempting to install the circuit breaker in 
the cell, verify that the continuous current, 
voltage and interrupting ratings are correct for 
the power system. 
 
Open the B9 grease provided and apply a 
coating to the ends of the six (6) primary stab 
fingers (Fig. 17). 
 
A portable lifter should be used for the insertion 
or removal of the circuit breaker if the 
compartment is above floor level.  Place the 
breaker on the lifter and bring it to the same 
level as the cell.  Align the hole on the lifter tab 
with the welded nut on the cell base and 
remove the holding pin from the right hand side 
of the cell base. (Fig. 18). 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Fig. 17  Apply B9 Grease to Stab Fingers 
 
 
 
 
 
 
 
Fig. 18  Lifter Positioned for Insertion of 
Breaker into Cell 
 
    