PRE-ENERGIZATION CHECK 
 
 
 
 
GENERAL 
 
BEFORE ENERGIZING THE CIRCUIT 
BREAKER 
for the first time, follow the procedure 
below to verify that the equipment is properly 
installed and functional. 
 
Hazardous Voltage. Turn off 
and lock out all primary and 
control circuit power 
sources prior to performing 
this pre-energization check. 
 
Do not operate this 
equipment until a complete 
safety inspection has been 
made. 
 
Do not energize damaged 
equipment that has not 
been repaired or verified. 
 
Do not remove, cover or 
destroy any safety signs. 
 
Do not operate this 
equipment until all panels 
and covers have been 
installed. 
 
 
 
All blocks or other temporary braces used for 
shipment must be removed. 
 
 
Before closing the enclosure, all metal chips, 
scrap wire and other debris left over from 
installation must be cleaned out. 
 
 
Cover all unused openings. Install all panels, 
guards and covers. 
 
  A supply of spare parts should be 
established. 
 
 
Instruction manuals and diagrams should be 
collected and filed.                     
 
 
 
 
 
 
 
 
 
ELECTRICAL CHECKS 
 
Electrical shock hazard.  
Do not touch energized 
components during a test 
using auxiliary power. 
 
 
An electrical insulation resistance test should 
be performed to verify that the circuit breaker 
and associated field wiring are free from 
short circuits and grounds. Refer to the 
MAINTENANCE Section of this manual for 
additional information. 
 
Hazardous voltages are 
present during dielectric 
testing which can result in 
serious injury or death.  
High potential tests should 
be performed only by 
qualified personnel. 
 
The circuit breaker must be set to the OFF 
position before energizing incoming power.
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
    
DANGER
 
    WARNING 
   WARNING
    WARNING 
    WARNING 
   WARNING
    WARNING 