Toshiba 18 - 1250 A Benutzerhandbuch

Seite von 99
TE Series        
          Digital Solid State Soft Starters   18 – 1250A 
16 
4.1.4   Testing 
The TE Series can be tested with a load smaller than the motor it was 
originally selected to control, however additional steps must be taken to 
avoid tripping on Phase Current Loss. See section 5.6.9.a under “Phase 
Loss Protection” for additional details on performing this task. 
ƒ  NOTE: 
The unit cannot be tested without a motor or other test load 
connected to the load side of the unit. It may be necessary to use a 
load bank to test the unit without a motor.  
ƒ  Line voltage will appear across the output terminals if there is no 
motor or load connected to the unit.  
ƒ IMPORTANT 
NOTE: 
Fault code SSd may display if there is no output load connection 
when control power is applied! 
 
4.1.5 Lightning 
Protection 
As with all electronic power controllers, protection from damage by 
lightning surges is recommended in areas where lightning is a 
significant problem. Stationary air gap lightning arrestors should be 
considered and utilized on the input power source. The best method of 
protection is to have an Isolation Contactor in front of the starter that is 
open when the soft starter is not in use. 
 
 
4.2  
Control Connections 
Control connections on the TE Series starter are divided into 2 groups. 
With the unit oriented vertically, TB1 is a 12-point DC terminal block (on 
the left), and TB2 is a 10 point AC terminal block (on the right side). 
These are removable terminal blocks for ease of connection and 
servicing, and are provided with different spacing (pitch) between the 
header pins so they are not interchangeable.  Following are descriptions 
of control connection points. 
 
ƒ  NOTE:  
Terminal numbers are shown on the side of the first and last 
terminal of each block. An additional 3 point terminal on the far left 
side is for serial communication connections (see section 5.6.11). 
 
 
 
 
 
 
 
 
 
 
 
 
 
N C
JOG
RAMP2
PTC
OPTO
24VDC from internal supply
240VAC max. from
customer source
TB1: 12 terminals, #1-12
TB2: 10 Terminals, #13-22
Opto-Isolated Triac Switch
10-250VAC/DC 50mA max.
1     2    3 ...............................................  11  12 13   14 ...........................19   20
1
NC  NO
.
C
1
A1  A2
2
NC  NO
.
C
3
NO
.
C
= Factory installed jumpers
120VAC Control Power
 (or 240VAC if ordered)