Toshiba 18 - 1250 A Benutzerhandbuch

Seite von 99
TE Series        
          Digital Solid State Soft Starters   18 – 1250A 
18 
4.2.2   Three-Wire Control Connection 
For standard 3-wire control, connect dry (voltage free) contacts of the 
Stop / Start buttons as shown on the diagram directly above the terminal 
strip. Connect the NO contact of the Start button to Terminal #1 (far left 
terminal), the common point between the Stop and Start to Terminal #2 
(2
nd
 from left) and the NC from the Stop button to Terminal #3 (3
rd
 from 
left).  
ƒ  4.2.2.a  
Seal In Contact 
The TE Series uses an internally pre-wired “seal-in” contact around 
the Start button (Terminals 1 and 2). No external relay or auxiliary 
output connection is necessary
 
4.2.3   Two Wire Control: Relay / PLC Connection 
An alternate connection for automated or unattended operation replaces 
start/stop push buttons by connecting a dry (voltage free) maintained 
contact closure between terminals 1 and 3 as shown in Figure 4.2.3. 
When this contact is closed, the TE Series starter will start and run. 
When it is opened, it is the same as a Stop command. 
 
ƒ  4.2.3.a  
Automatic Functions and 2 Wire Control 
If using the Time Clock functions (F032-F039) or Auto Reset 
functions (F052 – F053), special consideration must be given to 
using 2 wire control. Refer to Appendix 3 for additional details and 
information on time clock functions, and section 5.6.9 for details on 
using Auto-Reset functions. 
 
ƒ  NOTE:
  
When a maintained contact is used for start/stop it is advisable to 
set the overload relay to the manual reset position. This will prevent 
the motor from restarting if the thermal overload trips and then cools 
off. 
 
    CAUTION
  
Control Terminals 1-10 of TB1 are a 24VDC circuit from an internal 
power supply of the TE Series
Use dry (unpowered) contact closures only. Applying any voltage 
to these terminals will result in damage to the TE Series
 control 
board. 
If existing 120VAC or other powered control circuit must be 
interfaced, use interposing relays or control the TE Series
 with 2 
wire control as shown above. 
 
4.2.4   Interlock Connection 
TB1 provides a connection point for an external dry (voltage free) N.C. 
(Normally Closed) interlock device between terminals 4 and 5. 
Examples where this interlock connection would be used include low oil, 
high temperature, or excess vibration dropout from user supplied 
devices. A factory-installed jumper is provided which allows the TE 
Series
 unit to operate if external interlocks are not used. If this jumper is 
removed and an interlock is not used, the TE Series unit will not 
function. 
N C
JOG
RAMP2
PTC
OPTO
Connect 3 wire
control here
as shown
Figure 4.2.2
 3 Wire Control Connection
TB-1
1         2       3
N C
JOG
RAMP2
PTC
OPTO
Connect 2 wire
control / PLC
output here
Figure 4.2.3
 2 Wire Control Connection
TB-1
1         2       3
N C
JOG
RAMP2
PTC
OPTO
Remove factory jumper
and connect external
interlock device here
Figure 4.2.
 External Interlock Connection
TB-1
4          5