Toshiba 18 - 1250 A Benutzerhandbuch

Seite von 99
TE Series        
          Digital Solid State Soft Starters   18 – 1250A 
17 
Figure 4.2: Control Terminal Blocks 
 
 
4.2.1 AC Control Power Supply Connection 
 
Separate AC Control Power supply is required to power the electronics 
of the TE Series starter. 120VAC is standard, order 240 VAC (optional) 
if necessary for your line power supply configuration. The control 
voltage must be connected to terminals marked A1 and A2 of TB-2 as 
shown in figure 4.2.1 (these are also Terminal #s 21 and 22). This 
control voltage must be customer supplied, unless an optional control 
power transformer (see table below) has been supplied with the unit. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
ƒ  4
.2.1.a  
Control 
Power Requirements 
When sizing a control power transformer for the TE…-BP Series 
starter use the above chart for minimum sizes or supply capacity. 
Any additional control devices powered by the same CPT must be 
added to the above figures to ensure proper operation of the 
Bypass Contactor. 
 
ƒ  NOTE:  
TE-210 and larger units are available without the Bypass Contactor, 
but fans are still included. CPT can be sized for fan loads only if 
used in NEMA 1 ventilated enclosures. 
 
ƒ  4.2.1.b  
Control Fusing 
Output relays in TB2 must be protected from currents in excess of 
5A, either with a fuse or with other suitable current protection 
devices. 
ƒ  A dedicated fault output for use in PLC or interposing relay control 
is available on TB1. This opto-isolated Triac switch is rated for 
50mA max., 10-250V AC/DC. Any circuit connected to it must be 
fused accordingly. 
 
 
 
AC Control Power VA Requirements 
TE …-BP 
Model 
PC 
Boards 
Fans 
-BP: Bypass 
Contactor 
Inrush 
-BP: Bypass 
Contactor 
Sealed 
Recommended 
minimum  
CPT   
Rating 
TE-18 to 48 
48 
(inc. in PCB) 
95 
100 
TE-62 to 112 
48 
(inc. in PCB) 
220 
17 
250 
TE-150 to 160 
48 72  298  12.3 
500 
TE- 210 to 276* 
48 100  380  11.6 
500 
TE-360 to 450* 
48 150  571 
14 
750 
TE-550 to 900* 
48 200  600 
3.3 
750 
TE-1006 to 1250* 
48 
200 
1900 
48 
2000 
Table 3:  TE Series Control Power Requirements 
NOTE: *  - P versions (w/o bypass) still require PCB and fans, plus user supplied bypass (if any). 
120VAC
Supply
Figure 4.2.1
 Control Pow er Supply Connection
TB-2
1
NC  NO
.
C
1
A1  A2
2
NC  NO
.
C
3
NO
.
C