Toshiba 18 - 1250 A Benutzerhandbuch

Seite von 99
TE Series        
          Digital Solid State Soft Starters   18 – 1250A 
54 
ƒ  5.6.9.b  
Auto-Reset Programming (F052 – F054
The TE Series can be programmed to automatically attempt to 
reset after selected faults, provided a Start Command is present 
(see Section 4.2) and the fault condition has been corrected. The 
Fault Events to attempt restarting (F052) and number of reset 
attempts (F053) are programmable as follows. If F053 is set to 0 
(default setting), the TE Series will not attempt to restart 
automatically.  
ƒ  NOTE: 
When using 3 wire control:  
For safety reasons the TE Series will not attempt restarting unless 
the Start Command is reinitiated and maintained during a restart 
attempt.  
 
F052 =  Auto-Reset Selected Faults 
Factory Setting = 0 (Disabled) 
Range = 1 - 12, or 0 (Disabled) 
If F053 = 1 through 12, the TE Series will attempt to restart 
after the fault(s) coded in the following table. Only one selection 
can be entered. 
F053 
Setting
Fault Condition Description 
Display Readout  
Reference 
Auto Reset Disabled 
--- 
Over Temperature Trip 
OT 
Over Current (Shear Pin) Trip 
OC 
Under Current Trip 
UC 
Phase Loss Trip 
PLa or PLc 
Current Unbalance Trip 
UB 
Ground Fault Trip 
GF 
7 Short 
Circuit 
Trip 
SC 
Faults 1, 2 or 3 above 
OT, OC or UC 
Faults 4, 5 or 6 above 
PL, UB or GF 
10 
Any Fault except 7  
No SC 
11 
Any Fault except 6 & 7  
 No GF and no SC 
12 
Any Fault above, 1 - 7 
OT, OC, UC, PL, UB or GF  
1. NOTE 1: UC, OC or UB require operation to resume before the fault can be detected. 
2. NOTE 2: Cycling and / or restoration of control power will reset all of the above faults.  
3. NOTE 3: Overload Trip reset function is programmed only in F005. See Section 3 for details 
4. 
NOTE 4: Reset attempts that occur when the fault condition is still present will cause a new 
fault. This will be logged into the fault history (F085 – F093) and may overwrite previous fault 
records.
 
5. 
Line Loss Trip (see F051) will automatically reset and so is not included in this list.
Table 5.6.9.b:  Faults Selected for Auto-Restart  
 
F053 =  Auto-Restart Attempts 
Factory Setting = 0 (Disabled) 
Range = 1 - 10 Attempts, or 0 (Disabled) 
If F052 = 1 through 10, the TE Series will attempt to restart if 
the Start Command is present for this number of times. If set to 
Zero, the starter will not attempt to reset automatically.