          Digital Solid State Soft Starters   18 – 1250A 
55 
ƒ  5.6.9.c  
Timer Value Readouts for Protection Features 
F054 – F059 provide display of timer or register values for 
information only. The user cannot alter them. Upon power loss and 
restoration, these values are updated for time elapsed. 
 
F054 =  Restart Delay Time Readout 
Factory Setting = Not Applicable 
Range = 1 - 999 Seconds 
Remaining time value readout of F028, the Auto-Restart Delay 
Timer.  
F055 =  Coast Down (Backspin) Timer Value 
Factory Setting = Not Applicable 
Range = 1 - 3600 Seconds
 
Remaining time value readout of F048, the Coast Down 
Lockout Timer.  
F056 =  Starts per Hour Timer Value 
Factory Setting = Not Applicable 
Range = 1 - 3600 Seconds
 
Remaining time value readout of F049, the Starts-per-Hour 
Lockout Timer.  
F057 =  Starts per Hour Counter Readout 
Factory Setting = Not Applicable 
Range = 1 - 10 Starts 
Incremental counter value readout of F050, the Starts-per-Hour 
Lockout.  
F058 =  Time Value Between Starts Readout 
Factory Setting = Not Applicable 
Range = 1 - 3600 Seconds
 
Remaining time value readout of F050, the Minimum Time 
Between Starts Timer.  
F059 =  Thermal Capacity to Start Readout 
Factory Setting = Not Applicable 
Range = 0 - 100 % Thermal Capacity
 
Readout only for user’s viewing of the motor Thermal Capacity 
percentage required to allow a Reset after an Overload Trip. 
Use this function in conjunction with the Remaining Thermal 
Capacity (in the Status Screen group) to be able to predict 
when a restart will be allowed. This value is automatically 
updated by the TE Series CPU whenever a successful start 
sequence has been accomplished. The TE Series essentially 
“learns” how much Thermal Capacity is needed in the motor in 
order to successfully restart, and stores the information at this 
Function. Upon power loss and restoration, this value is 
updated for elapsed time.