Leupold Oven PS536GS Benutzerhandbuch

Seite von 44
15
E
N
G
L
IS
H
1.
Checking  the  Gas  Supply  (Inlet)  Pressure
a.
With  the  main  gas  supply  valve  closed  and  the  circuit
breaker/fused disconnect in the OFF ("O") position, open
the inlet pressure tap shown in Figure 2-16 and attach a
manometer to the tap.
b.
Depress the safety switches to allow the oven to operate.
c.
Open the main gas supply valve.  Switch the circuit breaker/
fused disconnect to the ON ("I") position.
d.
Start  the  oven  according  the  directions  in  the  Operation
section of this Manual.  Adjust the temperature controller to
the  maximum  setting  (316°C).
e.
Measure  the  supply  (inlet)  pressure.
f.
Switch the oven off.  Close the main gas supply valve, and
switch the circuit breaker/fused disconnect to the OFF ("O")
position.  Remove the manometer, and close the inlet tap.
g.
Compare  the  measured  supply  (inlet)  pressure  to  the
nominal pressures shown in Table 1-5 (in the Description
section of this Manual).
If  the  supply  pressure  is  lower  or  higher  than  the  nominal
pressure,  the  reason  should  be  investigated  and  the  gas
supplier  contacted.
For natural gas ovens, if the measured supply pressure is lower
than 0.247psi, or higher than 0.363psi, contact the gas supplier.
DO NOT OPERATE THE OVEN or adjust the oven controls.
2.
Adjusting the Orifice (Manifold) Pressure and Heat Input
To use the orifice pressure method, you must know the specific
gas type and quality used.  If using the orifice pressure method,
you should double-check the input using the volumetric method.
To use the volumetric method, you must know the heat value
(HuB) of the gas used.  This information is available from your
gas  supplier.
During  these  measurements,  do  not  operate  any  other
appliances  that  use  the  same  gas  meter  as  the  oven.
a.
Orifice (Manifold) Pressure Method
1.
With the main gas supply valve closed and the circuit
breaker/fused  disconnect  in  the  OFF  ("O")  position,
open the manifold pressure tap shown in Figure 2-16
and attach a manometer to the tap.
2.
Remove the cap screw from the pressure adjustment
screw (governor) on the gas control valve.
3.
Depress  the  safety  switches  to  allow  the  oven  to
operate.
4.
Open  the  main  gas  supply  valve.    Switch  the  circuit
breaker/fused disconnect to the ON ("I") position.
5.
Start the oven according the directions in the Operation
section of this Manual.  Adjust the temperature controller
to  the  maximum  setting  (316°C).
6.
Adjust  the  pressure  adjustment  screw  as  necessary
to  match  the  correct  pressure  for  the  oven's  specific
gas type.  Refer to Table 1-5 in the Description section
of this Manual.  Turning the adjustment screw clockwise
increases  the  flow,  while  turning  it  counterclockwise
reduces  the  flow.
7.
Switch the oven off.  Close the main gas supply valve,
and switch the circuit breaker/fused disconnect to the
OFF  ("O")  position.    Remove  the  manometer,  and
close  the  manifold  pressure  tap.
Consumption  (m
3
/hr.)  =
NB (Rated input in kW)
HuB (Heat [Calorific] value
of gas in kW/m3)
        =
Time  (in  minutes)  of
0.1m3  of  gas  usage
6
Consumption
SECTION 2 - INSTALLATION
b.
Volumetric  Method
1.
Determine the time of 0.1m
3
 (100 liters) of gas usage
as  follows.
2.
Check that the main gas supply valve and the circuit
breaker/fused disconnect are in the OFF ("O") position.
3.
Remove the cap screw from the pressure adjustment
screw (governor) on the gas control valve.
4.
Depress  the  safety  switches  to  allow  the  oven  to
operate.
5.
Open  the  main  gas  supply  valve.    Switch  the  circuit
breaker/fused disconnect to the ON ("I") position.
6.
Start the oven according the directions in the Operation
section of this Manual.  Adjust the temperature controller
to  the  maximum  setting  (316°C).
7.
Adjust  the  pressure  adjustment  screw  as  necessary
to  match  the  calculated  volume  using  the  time  (in
minutes)  of  0.1m
3
  of  gas  usage.    Turning  the
adjustment screw clockwise increases the flow, while
turning  it  counterclockwise  reduces  the  flow.
8.
Record the reading obtained from the gas meter and
calculate the obtained gas flow.  Compare this value
to  the  information  in  Tables  1-4  and  1-5  in  the
Description  section  of  this  Manual.
9.
Switch the oven off.  Close the main gas supply valve,
and switch the circuit breaker/fused disconnect to the
OFF ("O") position.  Replace the cap screw onto the
gas control valve.
Manifold
pressure tap
(where regulated
gas pressure is
measured)
Figure 2-16 - Gas Control Valve
Pressure adjustment
screw (under cap)