HP Performance Optimized Data Center (POD) 40cp Benutzerhandbuch
Site requirements 8
Callout Connection
2
Chilled water return connection
3
Chilled water supply connection
4
IT cable portals∗
∗
There are identical IT cable portals on the left side of the HP POD.
Work space requirements
IMPORTANT:
Failure to comply with the work space requirements can result in failed
authorization to power your HP POD by local electrical inspectors.
Work platform requirements
NOTE:
The base of the work platform should be level with the base of the HP POD. If you
choose to leave the HP POD on a trailer, a work platform is required.
The area outside of the HP POD directly in front of the panels must have a work platform. The
specifications of the work platform are:
•
The work platform must be a minimum of 1 m (3 ft) wide for standard platforms, and 1.1 m (3.5 ft)
wide if the work platform is constructed of grounded metal.
•
The work platform surface must be <2.0 m (6.6 ft) from the center of any circuit breaker actuator
handle.
Work space lighting
Make sure that the HP POD, transformer, switchboard, and water distribution kit are installed in a well lit
area that complies with local work space lighting requirements, per code regulations.
area that complies with local work space lighting requirements, per code regulations.
Environmental considerations
•
Install a properly engineered awning to enable access to the building in adverse weather conditions.
•
Install lightning protection for the HP POD.
•
Make sure that the HP POD is properly grounded.
•
Avoid placing the HP POD directly along a drainage path or in an area prone to flooding.
•
Raise the HP POD slightly off the ground, or set it on a higher point of elevation. In low elevated
areas, HP recommends setting the HP POD on a concrete housekeeping pad.
areas, HP recommends setting the HP POD on a concrete housekeeping pad.
•
Avoid placing the HP POD directly in the path of external heat loads such as a diesel generator or
an air cooled chiller.
an air cooled chiller.
Temperature considerations
The standard operating temperature for the HP POD is from -17.8°C to 54.4°C (0°F to 130°F).
If you choose to purchase the additional insulating paint ("
If you choose to purchase the additional insulating paint ("
operating temperature of the HP POD is from -28.9°C to 54.4°C (-20°F to 130°F).