Freeze Cycle – LED 1 is on. The compressor, fan motors and pump motor remain 
energized. The liquid line valves energize and the hot gas valves de-energize (also 
de-energizing the X1 relay). The lower float switch activates (open)  times during 
the course of a freeze cycle; the first is for refill, the second is for freeze termination. 
After the second lower float switch activation, the control board terminates freeze and 
initiates harvest. Every 10th cycle, the control board initiates a 10 second pump-out 
cycle between the freeze and harvest cycles. See "II.C.3.d) Pump-Out Frequency 
Control."
 a. 
Lower Float Switch 1st ActivationRefill – LEDs 1 and 4 are on. The refill can occur 
at any time during the freeze cycle (1 refill per cycle). As ice builds the water level 
drops in the reservoir and the lower float switch activates (opens). LED 4 comes on and 
the control board energizes the fill water valve. The fill water valve remains energized 
until the upper float switch closes or the 1 minute fill timer terminates, whichever comes 
first. 
b.
 Lower Float Switch 2nd Activation: LED 1 is on. The unit is held in freeze by a 
5 minute short cycle protection timer. After the 1st lower float switch activation and 
refill, ice continues to form and the water level drops in the reservoir. When the lower 
float switch activates (opens) a second time, the freeze cycle terminates (freeze 
can only be terminated on the second activation of the lower float switch and after 
5 minutes of freeze). 
Diagnosis: Minimum freeze time is 5 minutes. During the first 
5 minutes of freeze, confirm that the evaporator temperature drops, compressor, fan 
motors, pump motor, and liquid line valves are energized and that the hot gas valves, 
harvest water valve and fill water valve (except during refill) are de-energized and 
not bypassing. Make sure the expansion valves are operating properly and, in cold 
conditions, make sure the headmaster (C.P. Regulator) is operating correctly. Make 
sure that the drain water valve is not leaking by (water flowing down the potable drain). 
Check for proper unit pressures (see "III.C. Performance Data"), or an inoperative 
compressor. Disconnect the black K5 float switch connector from the control board. 
15 seconds after disconnecting the black K5 float switch connector, LED 4 comes 
on and refill begins. Connect the black K5 float switch connector back on the control 
board. When the refill is finished (LED 4 goes off), disconnect the black K5 float switch 
connector again. If 5 or more minutes have elapsed in the freeze cycle, the unit should 
switch out of the freeze cycle. After the unit switches out of freeze, reconnect the black 
K5 float switch connector to the control board. If the unit remains in freeze with the float 
switch disconnected, replace the board. To check the float switch, see "II.F.3. Float 
Switch Check Procedure."
 
Note: Normal freeze cycle will last 30 to 35 minutes depending on model and 
conditions. Cycle times and pressures should follow performance data provided 
in this manual.