6. Removal and Replacement of Thermistor
CAUTION
1. Fragile, handle very carefully.
. Always use a recommended sealant (high thermal conductive type), 
Model KE4560RTV manufactured by SHINETSU SILICONE, Part Code 
60Y000-11, or Part Code 4A0683-01 equivalent.
3. Always use a recommended foam insulation (Non-absorbent Type) or 
equivalent.
4. Do not shorten or cut the thermistor leads when installing.
1) Turn off the power supply.
) Remove the panels.
3) Remove the control box cover.
4) Disconnect the thermistor leads from the 
K3 connector on the control board.
5) Remove the plastic cable ties, foam 
insulation, thermistor holder and 
thermistor. 
6) Scrape away the old sealant on the 
thermistor holder and the suction pipe.
7) Wipe off moisture or condensation on the 
suction pipe.
8) Smoothly apply recommended sealant (KE4560RTV, Part Code 60Y000-11 or 
4A0683-01) to the thermistor holder concave.
9) Attach the new thermistor to the suction pipe in the same position as the previous 
thermistor. Be very careful to prevent damage to the leads. Secure it using the 
thermistor holder and recommended foam insulation.
10) Secure the insulation using plastic cable ties.
11) Connect the thermistor leads through the bushing of the control box to the K3 
connector on the control board.
Note: Do not shorten or cut the thermistor leads.
1) Replace the control box cover and the panels in their correct positions.
13) Turn on the power supply.
Foam Insulation   
Thermistor Holder
Thermistor Lead   
Cable Tie
 
Fig. 4