Honeywell NXL Benutzerhandbuch

Seite von 96
































                                      
                                  
                                  
                                  
Commissioning 
85(96) 
 
 
8.3 
Basic parameters 
On the next pages you will find the list of parameters that are essential for the commissioning of the 
frequency converter. You will find more details of these and other special parameters in the HVAC and in 
the Multi-Control Application manuals. 
 
 
Column explanations: 
Code 
=  Location indication on the keypad; Shows the operator the present param. number 
Parameter 
=  Name of parameter 
Min 
=  Minimum value of parameter 
Max 
=  Maximum value of parameter 
Unit 
=  Unit of parameter value; Given if available 
Default 
=  Value preset by factory 
Cust 
=  Customer’s own setting 
ID 
=  ID number of the parameter (used with PC tools) 
           
=  
On the parameter code: parameter value can only be changed after the FC has been 
stopped
.
 
 
8.3.1  Monitoring values (Control keypad: menu M1) 
The monitoring values are the actual values of parameters and signals as well as statuses and 
measurements. Monitoring values cannot be edited. See Chapter 7.4.1 for more information. 
 
Code 
Parameter 
Unit 
ID 
Description 
V1.1 
Output frequency 
Hz 
Frequency to the motor 
V1.2 
Frequency reference 
Hz 
25 
 
V1.3 
Motor speed 
rpm 
Calculated motor speed 
V1.4 
Motor current 
Measured motor current 
V1.5 
Motor torque 
Calculated actual torque/nominal torque of the unit 
V1.6 
Motor power 
Calculated actual power/nominal power of the unit 
V1.7 
Motor voltage 
Calculated motor voltage 
V1.8 
DC-link voltage 
Measured DC-link voltage 
V1.9 
Unit temperature 
ºC 
Heat sink temperature 
V1.10 
Analogue input 1 
13 
AI1 
V1.11 
Analogue input 2 
 
14 
AI2 
V1.12 
Analogue output current 
 
26 
AO1 
V1.13 
Analogue output current 1, expander board 
mA 
31 
 
V1.14 
Analogue output current 2, expander board 
mA 
32 
 
V1.15 
DIN1, DIN2, DIN3 
 
15 
Digital input statuses 
V1.16 
DIE1, DIE2, DIE3 
 
33 
I/O expander board: Digital input statuses 
V1.17 
RO1 
 
34 
Relay output 1 status 
V1.18 
ROE1, ROE2, ROE3 
 
35 
I/O exp. board:  Relay output statuses 
V1.19 
DOE 1 
 
36 
I/O exp. board: Digital output 1 status 
V1.20 
PID Reference 
20 
In percent of the maximum frequency 
V1.21 
PID Actual value 
21 
In percent of the maximum actual value 
V1.22 
PID Error value 
22 
In percent of the maximum error value 
V1.23 
PID Output 
23 
In percent of the maximum output value 
V1.24 
Autochange outputs 1, 2, 3 
 
30 
Used only in pump and fan control 
V1.25 
Mode 
 
66 
Shows the current operating mode selected with the 
Start-up Wizard: 1=Standard, 2= Fan, 3= Pump, 4= 
High Performance  
Table 8-1. Monitoring values