Commissioning 
Honeywell
Honeywell
Honeywell
Honeywell
 
 
 
8.3.2  HVAC parameters in NXL HVAC (Control keypad: Menu P2 




 B2.1) 
Code 
Parameter 
Min 
Max 
Unit 
Default** 
Cust 
ID 
Note 
P2.1.1 
Min frequency 
0,00 
Par. 2.1.2 
Hz 
0,00 
 
101 
 
P2.1.2 
Max frequency 
Par. 2.1.1 
320,00 
Hz 
50,00 
 
102 
NOTE: If f
max
 > than the 
motor synchronous speed, 
check suitability for motor 
and drive system 
P2.1.3 
Acceleration time 1 
0,1 
3000,0 
1,0 
 
103 
 
P2.1.4 
Deceleration time 1 
0,1 
3000,0 
1,0 
 
104 
 
P2.1.5 
Current limit 
0,1 x I
L
 
1,5 x I
L
 
I
L
 
 
107 
NOTE: Formulas apply 
approximately for 
frequency converters up to 
MF3. For greater sizes, 
consult the factory. 
P2.1.6 
Nominal current of 
the motor 
0,3 x I
L
 
1,5 x I
L
 
I
L
 
 
113 
Check the rating plate of 
the motor 
P2.1.7 
Nominal speed of 
the motor 
300
 
20000 
rpm 
1440
 
 
112 
The default applies for a 4-
pole motor and a nominal 
size frequency converter. 
P2.1.8 
Start function 
 
 
505 
0=Ramp 
1=Flying start 
2=Conditional Flying start* 
P2.1.9 
Stop function 
 
 
506 
0=Coasting 
1=Ramp 
P2.1.10 
Automatic restart 
 
 
731 
0=Not used 
1=Used (3 x automatic 
Restart) 
P2.1.11 
Nominal voltage of 
the motor 
380 
500 
400V 
 
110 
 
P2.1.12 
Nominal frequency 
of the motor 
30,00 
320,00 
Hz 
50,00 
 
111 
Check the rating plate of 
the motor 
P2.1.13 
Preset speed 1 
0,00 
Par. 2.1.2 
Hz 
10,00 
 
105 
 
P2.1.14  Parameter conceal 
0  
 
 
115 
0=All parameters and 
menus visible 
1=HVAC group P2.1 and 
menus M1 – H5 visible 
 
 
 
 
 
 
 
 
 
Table 8-2. HVAC parameters P2.1 in NXL HVAC 
Start mode where Trip Free Output Switching is enabled, recommended to be used with all pump and fan 
applications. 
** Default values if Start-up wizard has not been used. Look Figure 7-3 on page 54 or NXL HVAC Quick 
Guide
 to see the values with different modes in wizard. 
 
NOTE!
 Deactivating Parameter conceal P.2.1.14 gets all parameters into use in NXL HVAC drive