8.3.3  Basic parameters (Control keypad: Menu P2 




 B2.1 / B2.1.15) 
 
In NXL HVAC the full NXL basic group can be found under the subgroup 2.1.15.  
 
Code 
Parameter 
Min 
Max 
Unit 
Default** 
ID 
Note 
NXL 
Compact 
NXL 
HVAC 
 
 
 
 
 
 
 
P2.1.1 
P2.1.15.1 
Min 
frequency 
0,00 
Par. 2.1.2 
Hz 
0,00 
101 
 
P2.1.2 
P2.1.15.2 
Max 
frequency 
Par. 2.1.1 
320,00 
Hz 
50,00 
102 
NOTE: If f
max
 > than the 
motor synchronous speed, 
check suitability for motor 
and drive system 
P2.1.3 
P2.1.15.3 
Acceleration 
time 1 
0,1 
3000,0 
1,0 
103 
 
P2.1.4 
P2.1.15.4 
Deceleration 
time 1 
0,1 
3000,0 
1,0 
104 
 
P2.1.5 
P2.1.15.5  Current limit  0,1 x I
L
 
1,5 x I
L
 
I
L
 
107 
NOTE: Formulas apply 
approximately for 
frequency converters up to 
MF3. For greater sizes, 
consult the factory. 
P2.1.6 
P2.1.15.6 
Nominal 
voltage of 
the motor 
180 
690 
NXL2:230V 
NXL5:400V 
110 
 
P2.1.7 
P2.1.15.7 
Nominal 
frequency 
of the motor 
30,00 
320,00 
Hz 
50,00 
111 
Check the rating plate of 
the motor 
P2.1.8 
P2.1.15.8 
Nominal 
speed of 
the motor 
300 
20 000 
rpm 
1440 
112 
The default applies for a 4-
pole motor and a nominal 
size frequency converter. 
P2.1.9 
P2.1.15.9 
Nominal 
current of 
the motor 
0,3 x I
1,5 x I
L
 
I
113 
Check the rating plate of 
the motor 
P2.1.10 
P2.1.15.10  Motor cosϕ 
0,30 
1,00 
 
0,85 
120 
Check the rating plate of 
the motor 
P2.1.11 
P2.1.15.11  Start function 
 
505 
0=Ramp 
1=Flying start 
2=Conditional Flying start* 
P2.1.12 
P2.1.15.12  Stop function 
 
506 
0=Coasting 
1=Ramp 
P2.1.13 
P2.1.15.13 
U/f 
optimisation 
 
109 
0=Not used 
1=Automatic torque boost 
P2.1.14 
P2.1.15.14  I/O reference 
 
117 
0=AI1 
1=AI2 
2=Keypad reference 
3=Fieldbus reference 
    (FBSpeedReference) 
4=Motor potentiometer 
5=AI1/AI2 selection 
P2.1.15 
P2.1.15.15 
AI2 signal 
range 
 
390 
Not used if AI2 Custom min 
> 0% or AI2 custom max. < 
100% 
1=0mA – 20mA 
2=4mA – 20mA 
3=0V – 10V 
4=2V – 10V