Honeywell NXL Benutzerhandbuch

Seite von 96
88(96) 
Commissioning 
Honeywell
Honeywell
Honeywell
Honeywell
 
 
P2.1.16 
P2.1.15.16 
Analogue 
output 
function 
12 
 
307 
0=Not used 
1=Output freq. (0—f
max
2=Freq. reference (0—f
max
3=Motor speed (0—Motor 
nominal speed) 
4=Output current (0—
I
nMotor
5=Motor torque (0—T
nMotor
6=Motor power (0—P
nMotor
7=Motor voltage (0—
U
nMotor
8=DC-link volt (0—1000V) 
9=PI controller ref. value 
10=PI contr. act. value 1 
11=PI contr. error value 
12=PI controller output 
P2.1.17 
P2.1.15.17 
DIN2 
function 
10 
 
319 
0=Not used 
1=Start Reverse 
2=Reverse 
3=Stop pulse 
4=External fault, cc 
5=External fault, oc 
6=Run enable 
7
=Preset speed 2 
8= Motor pot. UP (cc) 
9= Disable PID (Direct freq. 
reference) 
10=Interlock 1 
P2.1.18 
P2.1.15.18 
DIN3 
function 
17 
 
301 
0=Not used 
1=Reverse 
2=External fault, cc 
3=External fault, oc 
4=Fault reset 
5=Run enable 
6=Preset speed 1 
7=Preset speed 2 
8
=DC-braking command 
9=Motor pot. UP (cc) 
10=Motor pot. DOWN (cc)  
11=Disable PID (PID 
control selection) 
12=PID Keypad ref. 2 
selection 
13=Interlock 2 
14=Thermistor input (See 
Chapter 6.2.4
15=Force CP to I/O 
16=Force CP to Fieldbus 
17=AI1/AI2 selection 
P2.1.19 
P2.1.15.19 
Preset 
speed 1 
0,00 
Par. 2.1.2 
Hz 
10,00 
105 
 
P2.1.20 
P2.1.15.20 
Preset 
speed 2 
0,00 
Par. 2.1.2 
Hz 
50,00 
106 
 
P2.1.21 
P2.1.15.21 
Automatic 
restart 
 
731 
0=Not used 
1=Used 
P2.1.22 
 
Parameter 
conceal 
0  
 
115 
0=All parameters and 
menus visible 
1=Only group P2.1 and 
menus M1 – H5 visible 
Table 8-3. Basic parameters P2.1 
Start mode where Trip Free Output Switching is enabled, recommended to be used with all pump and fan 
applications. 
** Default values if Start-up wizard has not been used. Look Figure 7-3 on page 54 or NXL HVAC Quick 
Guide
 to see the values with different modes in wizard. 
9. 
FAULT TRACING 
When a fault is detected by the frequency converter control electronics, the drive is stopped and the 
symbol F together with the ordinal number of the fault and the fault code appear on the display. The