Bradley Smoker PLC-5 Benutzerhandbuch

Seite von 388
Publication 1785-UM012D-EN-P - July 2005
Processor Status File        B-7
70
The controller detected duplicate labels
Non-recoverable
71
The controller tried to start an SFC subchart that is already running
72
The controller tried to stop an SFC subchart that isn’t running
73
The controller tried to start more than the allowed number of subcharts
74
SFC file error detected
75
The SFC has too many active functions
76
SFC step loops back to itself.
77
The SFC references a step, transition, subchart, or SC file that is missing, empty or too small
78
The controller cannot continue to run the SFC after power loss
79
You tried to download an SFC to a controller that cannot run SFCs
80
You have an I/O configuration error
81
You illegally set an I/O chassis backplane switch by setting both switch 4 and 5 on
82
Illegal cartridge type for selected operation. This error also occurs if the controller doesn’t 
have a memory module, but the backplane switches are set for a memory module. Make sure 
the backplane switches are correct (set switch 6 ON and switch 7 OFF if the controller 
doesn’t have a memory module).
83
User watchdog fault
Recoverable
84
Error in user-configured adapter mode block-transfer
Non-recoverable
85
Memory module bad
86
Memory module is incompatible with host
Non-recoverable
87
Scanner rack list overlap
88
Scanner channels are overloading the remote I/O buffer; too much data for the controller to 
process. If you encounter fault code 88, be sure you followed the design guidelines listed on 
page 4-9. Specifically, make sure you:
• group together 1/4-racks and 1/2-racks of each logical rack. Do not intersperse these with other 
rack numbers
• if using complementary I/O addressing, treat complementary rack addresses individually when 
grouping racks; primary rack numbers are separate from complement rack numbers
This 
Fault 
Code
Indicates this Fault
And the Fault Is