Bradley Smoker PLC-5 Benutzerhandbuch

Seite von 388
Publication 1785-UM012D-EN-P - July 2005
Processor Status File        B-9
S:13-S:24
This Word:
Stores
S:13
Program file where fault occurred
S:14
Rung number where fault occurred
S:15
VME status file
S:16
I/O status File
S:17Minor fault (word 2)
See also S:10.
S:17/00
BT queue full to remote I/O
S:17/01
Queue full - channel 1A; maximum remote block-transfers used
S:17/02
Queue full - channel 1B; maximum remote block-transfers used
S:17/03
Queue full - channel 2A; maximum remote block-transfers used
S:17/04
Queue full - channel 2B; maximum remote block transfers used
S:17/05
No modem on serial port
S:17/06
• Remote I/O rack in local rack table or 
• Remote I/O rack is greater than the image size. This fault can also be 
caused by the local rack if the local rack is set for octal density scan 
and the I/O image tables are smaller than 64 words (8 racks) each.
S:17/07
Firmware revision for channel pairs 1A/1B or 2A/2B does not 
match controller firmware revision
S:17/08
ASCII instruction error
S:17/09
Duplicate node address
S:17/10
DF1 master poll list error
S:17/11
Protected controller data table element violation
S:17/12
Protected controller file violation
S:17/13
Using all 32 ControlNet MSGs
S:17/14
Using all 32 ControlNet 1771 READ and/or 1771 WRITE CIOs
S:17/15
Using all 8 ControlNet Flex I/O CIOs
S:18
Controller clock year
S:19
Controller clock month
S:20
Controller clock day
S:21
Controller clock hour
S:22 
Controller clock minute
S:23
Controller clock second
S:24
Indexed addressing offset
S:25
Reserved