Publication 1785-UM012D-EN-P - July 2005
B-8        Processor Status File
90 
Sidecar module extensive memory test failed. Call your Allen-Bradley representative for 
service
Recoverable
91 
Sidecar module undefined message type
92 
Sidecar module requesting undefined pool
93 
Sidecar module illegal maximum pool size
94 
Sidecar module illegal ASCII message
95 
Sidecar module reported fault, which may be the result of a bad sidecar program or of a 
hardware failure
96 
Sidecar module not physically connected to the PLC-5 controller
97 
Sidecar module requested a pool size that is too small for PC
3
 command (occurs at power-up)
98 
Sidecar module first/last 16 bytes RAM test failed
99 
Sidecar module-to-controller data transfer faulted
100
Controller-to-sidecar module transfer failed
101
Sidecar module end of scan transfer failed
102
The file number specified for raw data transfer through the sidecar module is an illegal value
103
The element number specified for raw data transfer through the sidecar module is an illegal 
value
104
The size of the transfer requested through the sidecar module is an illegal size
105
The offset into the raw transfer segment of the sidecar module is an illegal value
106
Sidecar module transfer protection violation; for PLC-5/26, -5/46, and -5/86 controllers only
This 
Fault 
Code
Indicates this Fault
And the Fault Is