Utica Boilers UB95M-200 Verweisanleitung

Seite von 20
12
Para.
Name
Range
Boiler Display
Description
Gascom 
Software
Boiler
Display
Display Position
1st
2nd
3rd
4th
1
t3 Set
Storage dHW: 
68° to 158°F
instantaneous  
dHW:
104° to 150°
68 to 158 
104 to 150
1
Setting
 • T3 is the DHW temperature by an immer-
sion sensor. 
•  DO  NOT  CHANGE  this  parameter  from 
the  factory  setting.  (  Boiler  outlet  water 
temperature setpoint in dHW mode is de-
termined by adding Parameter 1 to Param-
eter 33.)
• If applied for instantaneous DHW opera-
tion (not recommended), set Parameter 35 
for the correct configuration.
2
dHW System
dHW OFF
0
2
Blank
Blank
Value
•  Parameter  2  determines  whether  DHW 
heating is activated. the boiler will not op-
erate in dHW mode if this parameter is set 
to “0” or “3”.
dHW On
1
dHW OFF + 
pump
constant
2
• 
WARNING-  it  is  not  recommended  to 
set this parameter to either “2” or “3” (con-
tinuous  dHW  pump).  this  could  result  in 
a hazardous condition, because it causes 
constant circulation between the boiler and 
the dHW heater.
dHW On +  
pump
constant
3
3
CH System
CH OFF
0
3
Blank
Blank
Value
• Parameter 3 determines whether the boil-
er will operate in central heating mode.
CH On
1
CH OFF + 
boiler pump 
constant
2
• Select “1” to cycle the boiler circulator on 
central heating calls.
CH On + 
boiler pump 
constant
3
• Select “2” or “3” to maintain constant boil-
er circulation operation.
4
t1 top
120° to 194°F
68 tO 182
4
Setting
•  Constant  Boiler  Temperature  operation 
(outside sensor not connected): t1 top is 
the  target  outlet  water  temperature  at  all 
times.
• Outside reset (outside sensor connected): 
t1 top is the maximum water temperature  
based on outdoor air temperature.
5
t1 Foot
60° to 140°F
60 to 140
initial reading:
• T1 Foot applies only in outdoor reset op-
eration.
P
.
0
5
after 2 to 3 seconds:
• T1 Foot is the minimum target tempera-
ture for all outside  temperatures.
Blank
Setting
6
t4 minimum
-4° to 50° 
-4 to 50
initial reading:
• T4 Minimum applies only in outdoor reset 
operation.
P
.
0
6
after 2 to 3 seconds:
• T4 Minimum is the outside temperature at 
which  the  target  outlet  water  temperature 
is at maximum.
Blank
Blank
Setting
7
t4 maximum 
60° to 78°F
60 to 78
initial reading:
• T4 Maximum applies only in outdoor re-
set operation
P
.
0
7
after 2 to 3 seconds:
• T4 Maximum is the outside temperature 
at  which  the  target  outlet  water  tempera-
ture is at minimum.
Blank
Blank
Setting
V - PARAMETER REFERENCE TABLE