Utica Boilers UB95M-200 Verweisanleitung

Seite von 20
5
DO NOT CHange any PaRameteR unLeSS tHe aPPLiCatiOn RequiReS SPeCiaL SettingS.
PARAMETER/DESCRIPTION
GASCOM
DISPLAy
1
t3 Set dHW
150°F
150
2
dHW System
On
01
3
CH System
On
01
4
t1 top CH-mode
180°F
180
5
t1 Foot CH-mode
120°F
120
6
t4 minimum
0°F
00
7
t4 maximum
60°F
60
8
t4 Frost Protection
-20°F
-20
9
t4 Correction
0°F
00
10
t Blocking
60°F
60
11
Booster time
30 minutes
30
12
t Parallel Shift
10°F
10
13
maximum Fan Speed CH
6000 rpm
60
15
maximum Fan Speed dHW
6000 rpm
60
17
minimum Fan Speed
2250 rpm
22
19
ignition Fan Speed
3500 rpm
35
20
CH Postpump time
0 minutes
00
21
dHW Postpump time
30.6 Seconds
03
22
CH modulation Hysteresis On
4°F
04
23
CH modulation Hysteresis Off
4°F
04
24
dHW modulation Hysteresis On
4°F
04
25
dHW modulation Hysteresis Off
4°F
04
26
dHW detection Hysteresis On
4°F
04
27
dHW detection Hysteresis Off
4°F
04
28
CH Blocking time
10.2 Seconds
01
29
dHW Blocking time
10.2 Seconds
01
30
dHW -> CH Blocking time
30.6 Seconds
03
31
modulate Back difference t1 - t2
50°F
50
32
RmCi address
-01
-01
33
t Plus: Setvalue additional For dHW
30°F
30
34
2nd CH-Circuit (1st digit)
2nd CH-Circuit Off
00
34
CH type (2nd digit)
Room thermostat
00
35
dHW 3-Way Valve/Pump (1st digit)
Hot Water Pump
13
35
dHW type (2nd digit)
Storage tank w/out tank 
Sensor (ntC3)
13
36
manual Fan Speed
negative 1%
-01
37
PWm-Pump Level (1st digit)
3
31
37
PWm-Pump Level (2nd digit)
1
31
38
t Set Hold Boiler Warm
40°F
40
39
t top For 2nd CH Circuit
70°F
70
40
t Foot for 2nd CH Circuit
50°F
50
41
t Hysteresis For 2nd CH Circuit
20°F
20
42
Pump Settings For CH & dHW
00
21
42
minimum Off Cycle
not active
21
II - OVERVIEW OF CONTROL PARAMETERS
DEFAULT REV C PARAMETER SETTINGS ON GASCOM SOFTWARE AND BOILER DISPLAy