OUTDOOR RESET OPERATION
Outdoor reset adjusts the supply water temperature so the 
heat output from the heating units matches the heat loss as 
the outdoor temperature changes. the colder the outdoor 
temperature, the warmer the water temperature, and vice 
versa.
the closer the heating unit output matches the heat loss, 
the less the swing in the indoor temperature. you can adjust 
control parameters to do this as shown below.
OUTDOOR RESET TERMINOLOGy
Outdoor Design Temperature (ODT): 
• 
Outdoor design 
temperature for the area, used to calculate heat loss. 
(Use this value for T4 minimum.)
Balance Point Temperature
• 
Outside temperature 
at which building heat loss equals building heat gain 
from solar and internal sources. at this temperature, 
no space heating is required. (Use this value for T4 
maximum.)
 
Automatic Temperature Boost: 
• 
Compensates for 
side temperature.
t1 top (Parameter 4) is the outlet water temperature 
the boiler tries to maintain whenever the outside tem-
IMPORTANT:  installation  must  comply  with  local  re-
quirements and with the national Fuel gas Code, anSi 
Z223.1  for  u.S.  installations  or  CSa  B149.1  or  B149.2 
for Canadian installations.
required pick-up times and variations in heating load 
requirements by automatically increasing set point tem-
perature when a call for heat exceeds a specified time 
(Parameter 11).
Parameters 4, 5, 6 & 7 (Outdoor reset)
Fixed Temperature Operation
• 
: if boiler is operated 
with constant outlet temperature (no outside tempera-
ture sensor installed), set Parameter 4 as described in 
this manual.
Outdoor Reset Operation:
• 
 Parameters 4 to 7 deter-
mine the reset curve, as shown in Figure #1.
t1 is the boiler outlet water temperature. t4 is the out-
• 
III - PARAMETER ExPLANATIONS
CONTROL MODULE PARAMETERS AND OUTDOOR 
RESET CURVE 
Outdoor Reset Example A
180°F
182°F
210°F
200°F
T4 Maximum 
(Parameter 7)
T Blocking
(Parameter 10)
 
T1 Foot
(Parameter 5)
(No higher that 180°F )
(Auto rest limit setting - not adjusted)
(Manual rest limit setting - not adjusted)
Boiler shuts OFF when
(T1 Set is less than T Blocking)
T4 Minimum
(Parameter 6)
T1 Top
(Parameter 4)
T1 Top
Cooler
W
armer
Setpoint T
emperature T1
Cooler
Warmer
Outside Temperature °F 
PARAMETER DETAILS
PARAMETER 
NUMBER
PARAMETER 
NAME
FACTORy 
SETTING
ADJUSTMENT 
RANGE
4
T1 Top
180°F
68 - 182°F
5
T1 Foot
120°F
60 - 140°F
6
T4 Minimum
0°F
-4 - 50°F
7
T4 Maximum
60°F
60 - 78°F
10
T Blocking
60°F
32 - 140°F
(or “32” for Off)
Figure #1
This document must only be used by a qualified 
heating installer or service technician. Read all 
instructions,  including  the  Installation  Manu-
al  (P/N#  240006103),  the  Control  Manual  and 
Operating  Instructions  (P/N#  240006104),  the 
User’s  Information  Manual  (P/N#  240006106), 
and this Parameter Guide before attempting to 
program the control, and be sure to perform all 
steps in the order specified. Failure to comply 
could result in severe personal injury, death, or 
substantial property damage.
WARNING
!
  
Revise  boiler  control  parameters  only  if  you 
fully understand the purpose and result of the 
changes  and  on  the  advice  of  Technical  Sup-
port.  Tampering  without  fully  understanding 
the control settings in this manual will void the 
warranty and can result in unreliable operation, 
with possible severe personal injury, death, or 
substantial property damage.
WARNING
!