Utica Boilers UB95M-200 Installationsanweisungen

Seite von 28
4
3. 
DHW heating: Target temperature is determined by 
adding Parameter 1 to Parameter 33 (default 150°F 
and 30°F). Do not change Parameter 1 from factory 
default setting of 150°F unless application is specially 
engineered for other temperature. DHW heating default 
setting is 180°F.
4. 
High limit operation: If outlet water temperature 
exceeds target temperature (or 180°F, whichever is 
lower), high limit action occurs. Control module shuts 
burner off showing “b 9” followed by “26” on display.
5. 
DHW operation (if used): Boiler is factory set to 
change target outlet water temperature to 180°F on 
call for heat from DHW aquastat.
6. 
Additional Thermal Overrun Protection: High 
limit operation shuts down burner when outlet 
water temperature exceeds target temperature.                  
Adverse conditions could cause water temperature 
to rise too quickly and overshoot this temperature. 
Control’s advanced technology provides protection in 
event of thermal overrun. Using its electronics, control 
provides two additional levels of overrun protection:
• Level 1: Indication occurs if supply water temperature 
reached 183°F.  Control displays soft lockout code (“b 
9” followed by “18” if on supply or “19” if on return). 
Control will not operate burner again until water 
temperature dropped 9°F below target temperature.
• Level 2: Lockout occurs if supply water temperature 
reaches 200°F or if return water reaches 193°F. Control 
will enter hard lockout and display error code (“E” 
followed by “18” if on supply or “19” if on return).
NOTICE
Hard lockout requires manually pressing display panel 
reset button to restart operation. Service technician 
must troubleshoot cause of problem and correct it 
before placing boiler back in operation.
Low Water/Low Flow Protection
1. 
Boiler is factory equipped with manual reset probe type 
low water cutoff. 
2. 
Boiler control uses temperatures sensed at both supply 
and return areas of heat exchanger. If flow rate is 
too low (temperature difference too high) or either 
temperature is too high, control shuts boiler down. 
Ensures boiler shutdown in event of low water or low 
flow conditions.
Freeze Protection
Do not install boiler in room likely to freeze.
Following boiler control feature provides some protection for boiler 
only, not for the system. 
Boiler is controlled by microprocessor electronic control that 
senses: 
• Outlet water temperature, 
• Return water temperature,
• Outdoor temperature (when factory supplied, field 
installed outdoor sensor is installed).
Information sensed plus input from external limit and 
operating controls is used to regulate boiler on/off 
operation and will modulate boiler firing rate to more 
closely match output to demand.
Electrical Specifications
Boilers require 120 VAC/60 HZ power supply and are not 
polarity sensitive.
CONTROL SPECIFICATIONS
Supply voltage
120 Vac/60 hz
Electrical demand
10 VA
Pre-purge timing
10 Seconds
Post-purge timing
15 Seconds 
Min. off time, space heating
10.2 Seconds
Pump on after space htg.
0 Minutes
Min. off time, DHW
10.2 Seconds
Pump on after DHW
30.6 Seconds
Line voltage fuse, F1
5 Amp fast-blow
Low voltage fuse, F3
4 Amp slow-blow
Boiler Circulator
• Circulator has sufficient head to handle boiler pressure 
drop plus reasonable pressure drop in connecting 
piping. See the Installation, Operation and Maintenance 
Manual for piping information.
• Boiler control’s internal relay contact is suitable for 
handling only the boiler circulator provided. 
• Do not wire additional pumps in parallel with boiler 
circulator.  
• To operate system circulator when boiler circulator is 
running, see “Electrical Wiring” section in Installation, 
Operation and Maintenance Manual for wiring required.
Boiler Temperature Regulation
Operating temperature (target): Control senses outlet water 
temperature and regulates boiler firing rate to achieve 
target temperature set by installer using Parameter 4. 
Temperature can be set between 120°F and 194°F.
1. 
Space heating: Target temperature is fixed (equal 
to Parameter 4) when outdoor reset is not installed 
or calculated as described under “Outdoor Reset 
Operation”  page 5, when outdoor sensor is connected.
2. 
Exception: See explanation of “Supply Temperature 
Boost” page 5.
3 - OPERATING INFORMATION