Omron CompoBus/D (DeviceNet) Communications Card 3G3FV-PDRT1-SIN Benutzerhandbuch

Seite von 161
5-50
Note 1. The default setting depends upon the type of Inverter. The value for a 200-V-class 0.4 kW
Inverter will be displayed.
Note 2. These are values for a 200-V-class Inverter. Values for 400-V-class Inverter are double.
D
Operator (o) Parameter Constants
Constant
Name
Regis-
Setting
Setting
Default
Chang
Control mode setting
ter No.
unit
range
setting
es dur-
ing op-
eration
V/f
control
V/f with
PG
Open
loop
vector
Flux
vector
o1-01
Monitor selection
0500
1
4 to 28
6
Yes
Yes
Yes
Yes
Yes
o1-02
Monitor selection after
power-on
0501
1
1 to 4
1
Yes
Yes
Yes
Yes
Yes
o1-03
Frequency reference
setting and display
units
0502
1
0 to 39,999
0
No
Yes
Yes
Yes
Yes
o1-04
V/f pattern setting
units
0503
1
0, 1
0
No
No
No
No
Yes
o1-05
Not used
0504
1
---
0
---
---
---
---
---
o2-01
Local/Remote Key
0505
1
0, 1
1
No
Yes
Yes
Yes
Yes
o2-02
Stop Key
0506
1
0, 1
1
No
Yes
Yes
Yes
Yes
o2-03
User constant initial
values
0507
1
0 to 2
0
No
Yes
Yes
Yes
Yes
o2-04
Inverter capacity
selection
0508
Hex
0 to FF (See
note.)
0 (See
note.)
No
Yes
Yes
Yes
Yes
o2-05
Frequency reference
setting method
0509
1
0, 1
0
No
Yes
Yes
Yes
Yes
o2-06
Operation selection
when Digital Operator
is disconnected
050A
1
0, 1
0
No
Yes
Yes
Yes
Yes
o2-07
Cumulative operation
time setting
050B
1
0 to 65,635
0
No
Yes
Yes
Yes
Yes
o2-08
Cumulative operation
time selection
050C
1
0, 1
0
No
Yes
Yes
Yes
Yes
o2-09
Factory use
050D
1
---
0
---
---
---
---
---
Note The default setting depends upon the type of Inverter. The value for a 200-V-class 0.4 kW Inverter
will be displayed.
CompoBus/D Communications Card Operations
Chapter 5