Configuring the FieldServer as a Secutron Modul-R driver Client 
For  a  detailed  discussion  on  FieldServer  configuration,  please  refer  to  the  FieldServer  Configuration 
Manual.  The information that follows describes how to expand upon the factory defaults provided in the 
configuration files included with the FieldServer (See “.csv” files on the provided with the FieldServer). 
 
This  section  documents  and  describes  the  parameters  necessary  for  configuring  the  FieldServer  to 
communicate with Secutron Modul-R panels.  
 
The configuration file tells the FieldServer about its interfaces, and the routing of data required.  In order 
to  enable  the  FieldServer  for  Secutron  Modul-R  driver  communications,  the  driver  independent 
FieldServer  buffers  need  to  be  declared  in  the  “Data  Arrays”  section,  the  destination  device  addresses 
need to be declared in the “Client Side Nodes” section, and the data required from the Servers needs to 
be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below. 
 
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default. 
 
4.1. 
Data Arrays/Descriptors 
 
Section Title 
Data_Arrays 
Column Title 
Function 
Legal Values 
Data_Array_Name 
Provide name for Data Array 
Up 
to 
15 
alphanumeric 
characters 
Data_Format 
Provide  data  format.  Each  Data  Array  can  only  take 
on one format. 
Bit,  Byte,  Packed_Bit, 
Uint16 
Data_Array_Length 
Number of Data Objects. Must be larger than the data 
storage area required for the data being placed in this 
array. 
1-10,000 
 
Example 
 
//    Data Arrays 
 
 
 
 
 
Data_Arrays 
 
 
Data_Array_Name, 
Data_Array_Format, 
Data_Array_Length 
p1c1_devices, 
Bit, 
p1c1_function, 
Byte, 
1000 
p1c69_restart, 
Bit, 
1000 
p1c69_function, 
Byte, 
100 
p1c90_reset, 
Bit, 
100 
p1c90_function, 
Byte, 
100 
 
The Poller Data Array will contain non-zero data when communications with the panel is OK.