Emerson 2200S User Manual

Page of 158
68
Micro Motion
®
 Model 2200S Transmitters
Integrating the Meter with the Control System
Note: Whenever you use ProLink II to set the HART address to 0, ProLink II also enables the Loop 
Current Mode parameter (places a check in the checkbox). Whenever you use ProLink II to set the 
HART address to any other value, ProLink II also disables the Loop Current Mode parameter. Be sure 
to verify the Loop Current Mode setting after you configure the transmitter’s HART address.
Note: Whenever you use the Communicator to set the HART address to 0, Loop Current Mode is 
automatically enabled. Whenever you use the Communicator to set the HART address to any other 
value, Loop Current Mode is automatically disabled. If you need to change this, first set the HART 
address as required, then use ProLink II to configure Loop Current Mode.
Configuration
To configure the Loop Current Mode parameter:
Using ProLink II, click 
ProLink > Configuration > Device
.
Note: You cannot configure Loop Current Mode with the display or the Communicator.
6.3.3
PV, SV, TV, and QV assignments
In the transmitter, four variables are defined for HART communications: the PV (primary variable), 
the SV (secondary variable), the TV (tertiary variable), and the QV (quaternary variable). A process 
variable such as mass flow is assigned to each HART variable. 
The values of the assigned process variables can be reported or read in several ways:
The PV is automatically reported through the mA output. It can also be queried via digital 
communications or reported via burst mode. If you change the PV, the process variable 
assigned to the mA output is changed automatically, and vice versa. See Section 6.2.1.
The SV, TV, and QV are not reported through an output. They can be queried via digital 
communications or reported via burst mode.
Table 6-7 lists the valid assignments for the PV, SV, TV, and QV on the Model 2200S transmitter. 
Table 6-6
Process variable assignments for PV, SV, TV, and QV
Process variable
PV 
SV
TV
QV
Mass flow rate
Volume flow rate
Temperature
Density
Gas standard volume flow rate
Drive gain
Mass total
Volume total
Mass inventory
Volume inventory
Board temperature