Emerson 2200S User Manual

Page of 158
Configuration and Use Manual
69
Integrating the Meter with the Control System
Op
eratio
n
App
e
ndi
ces
Mai
n
tenan
c
e and
 T
roub
le
sh
oo
tin
g
Com
m
is
si
on
in
g
Configuration
To configure the PV, SV, TV, and QV assignments:
Using the Communicator:
-
To configure the PV, assign the desired process variable to the mA output. See 
Section 6.2.1
-
To configure the SV, TV, and QV, select 
Detailed Setup > Config Outputs > 
HART Output
.
Using ProLink II, click 
ProLink > Configuration > Variable Mapping
.
6.3.4
Burst mode
Burst mode is a specialized mode of communication during which the transmitter regularly broadcasts 
HART digital information over the mA output. Burst mode is ordinarily disabled, and should be 
enabled only if another device on the network requires burst mode communication.
Note: If burst mode is enabled, HART/Bell 202 communications via a HART modem (as required by 
ProLink II) may be very slow, or the HART connection may fail completely. If either of these occurs, 
disable burst mode, use a communications tool that does not require a HART modem (i.e., the 
Communicator), try a HART modem from a different vendor, or try a USB HART modem. Ensure that 
RTS line control is managed by the modem.
Configuration
To configure burst mode:
1. Navigate to the correct menu:
If you are using the Communicator, select 
Detailed Setup > Config Outputs > 
HART Output
.
If you are using ProLink II, click 
ProLink > Configuration > Device
.
Note: You cannot configure burst mode with the display.
2. Enable burst mode.
3. Specify the Burst Mode Output. Options are described in Table 6-7.
4. If you specified 
Transmitter vars 
or 
Fld dev var
 in Step 3, specify the four process variables 
to be sent in each burst.
Gas standard volume inventory
Gas standard volume total
LPO amplitude
RPO amplitude
Raw tube frequency
Live zero
Table 6-6
Process variable assignments for PV, SV, TV, and QV continued
Process variable
PV 
SV
TV
QV