GROUNDING METER ELECTRONICS HOUSING
Section 3: Electrical installation
Daniel 3410 Series Ultrasonic Gas Flow Meter Installation Manual
June 2014
3-9000-759 Rev D
3.3
Grounding meter electronics housing
The meter electronics should be internally grounded for intrinsically safe operations. Connect a 
wire to the chassis ground lug installed inside the Transmitter Electronics Enclosure as the 
primary ground. A secondary ground is located outside of the Transmitter Electronics Enclosure 
(
). 
Figure 3-1  Internal Transmitter Electronics Enclosure chassis ground
The internal grounding terminal shall be used as the primary equipment ground. The 
external terminal is only a supplemental bonding connection where local authorities permit 
or require such a connection. DO NOT connect digital grounds to the ground lugs.
A. Transmitter Electronics Enclosure ground lug