A&D AD-4405 User Manual

Page of 80
 Page 
68 
AD-4405 Weighing Indicator
 
 
18.
18.
18.
18.     Relay Output & Control Input (O
Relay Output & Control Input (O
Relay Output & Control Input (O
Relay Output & Control Input (OP
P
P
P-
-
-
-05)
05)
05)
05)    
  Replacing the RS-232C interface with this option, 3-relay outputs and 3-control inputs 
can be used with the RS-232C interface of this option. 
  RS-232C functions and pin connections are the same as the RS-232C interface 
described in “16. RS-232C Interface”. 
  The control inputs can control the indicator from an external terminal just like the front 
panel key operations. 
  Set the external control functions at f13, f14 and f15 of the F-Functions. 
  When connecting each function pin to the common pin, the indicator makes the action. 
  Keep a signal width more than 100 ms for the On-time and Off-time. 
 
   
ON(Make) 
More than 100 ms  More than 100 ms 
 
  OFF(Break) 
  The relays output the result of comparison. 
Solid-state-relay 
Maximum voltage 
DC50V 
Maximum current 
DC100mA 
Maximum resistance  8
9
 
  Pin connections (DIN 8pin connector) 
Function 
Pin No.  Signal name
Direction
Description 
HI 
Output 
Relay output HI 
OK 
Output 
Relay output OK 
LO 
Output 
Relay output LO 
Relay 
output 
8 COM(out) - 
Relay 
common 
terminal 
EXT1 
Input 
Control input 1 (f13) 
EXT2 
Input 
Control input 2 (f14) 
EXT3 
Input 
Control input 3 (f15) 
Control 
input 
COM(in) 
Control input common 
  Adaptable connector 
JA-TCP0586 (of accessory) 
Circuits
Circuits
Circuits
Circuits    
 
HI
OK
LO
COM(out)
EXT3
EXT2
EXT1
+7 to 9V
680
9
680
9
680
9
COM
(in) 
DIN connector 
of OP-05 
Control input 
Relay output